Nomenclature Nomenclature FWW 02 L - A C E Revision AA: Revision 1 AB: Revision 2 Specification E: Cooling Only H: Cooling and Heating Market C: Export with CE Mark E: Export without CE Mark Power Supply A: 220-240V/1Ph/50Hz F: 380-415V/3Ph/50Hz Product Series L: L series (for FWW) D: D series (for FWE)
Page 6
Nomenclature FWC 03 C - A C A A A Revision A: Revision 1 B: Revision 2 Water Pipe Connection A: Right Piping B: Left Piping Controller A: With Controller N: Without Controller Market C: Export with CE Mark E: Export without CE Mark Power Supply A: 220-240V/1Ph/50Hz F: 380-415V/3Ph/50Hz...
Page 7
Nomenclature FWC 20 F D - A E 5 C R F A X A A Revision A: Revision 1 B: Revision 2 Insulation Material/Thickness A: PE/Drain Pan Standard;Return Air Plenum Without Insulation K: NBR/Drain Pan Standard;Return Air Plenum Without Insulation Motor/Control Module/Wired Controller X: AC/Without Control Module/...
Page 8
Nomenclature FWC 10 H - A J 5 C X X A X D A Revision A: Revision 1 B: Revision 2 Insulation Material/Thickness D: PE (10mm) G: PE (20mm) K: NBR (10mm) R: NBR (20mm) Motor/Control Module/Wired Controller X: AC/Without Control Module/ Without Wired Controller Drain Pan Material &...
Application Information Application Information Model: FWW Operating Limits: Thermal carrier : Water Water temperature : 4°C ~ 10°C (Cooling), 35°C ~ 50°C (Heating) Maximum water pressure : 16 bar Air temperature : (as below) Cooling Mode Heating Mode Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F...
Page 12
Application Information Model: FWC-C Operating Limits: Thermal carrier : Water Water temperature : 4 ~ 10°C (Cooling), 35°C ~ 50°C (Heating) Maximum water pressure : 16 bar Air temperature : (as below) Cooling Mode Heating Mode Temperature Ts °C/°F Th °C/°F Temperature Ts °C/°F Th °C/°F...
Application Information Installation Guide System Configuration The standard controller board comes with a VALVE jumper and a HEAT jumper. The system can be configured as the jumper selection listed below: HEAT Jumper VALVE Jumper Heatpump Mode & Valve Application √ √...
Page 14
Application Information Model: FWF/FWK/FWE/FWC-C CN_DRY LIVE CN_TW CN_PGRM CN_STP CN_DSP H_SEN C_SEN ROOM CN_WIR Valve Jumper Heat Jumper Fan Priority Jumper Jumper With Jumper (Default) Without Jumper User set speed or lower fan if auto Fan Priority Jumper Fan Stop when thermostat cat off mode is selected Heat Jumper For Heat pump...
Page 15
Application Information The standard controller board (W3) comes with a default setting for model selection. Please select the model accordingly by using jumper. System Model Function 2 Pipe M1 - Cooling or Heating System Model 1 Mini Chiller (Cooling Only) M2 - Cooling or Heating with Auxiliary Heater Model 2...
Page 16
Application Information Indoor Installation Model: FWW-L The indoor unit must be installed in such a way so as to prevent short circuit of the cool discharged air with the hot return air. Please follow the installation clearance shown in the figure. Do not place the indoor unit where there could be direct sunlight shining on it.
Page 17
Application Information Mounting Installation Plate Ensure that the wall is strong enough to withstand the weight of the unit. Otherwise, it is necessary to reinforce the wall with plates, beams or pillars. Use the level gauge for horizontal mounting, and fix it with 5 suitable screws for FWW02/03/04L and 7 suitable screws for FWW05/06L.
Page 18
Application Information Unit Installation • Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and fix the hanging rod. • The installation template is extended according to temperature and humidity. Check on dimensions in use. •...
Page 19
Application Information Drain Test • Connect the main drain pipe to the flexible drain. • Feed water from flexible drain hose to check the piping for leakage. • When the test is completed, connect the flexible drain hose to the drain connector on the indoor unit. Feed Water Main Drain Pipe Flexible Drain Hose...
Page 20
Application Information Model: FWE08/10/12E Standard Mounting Ensure that the overhead supports are strong enough to hold the weight of the unit. Position the hanger rods (wall mounting bracket for floor standing), and check for its alignment with the unit. Also, check that the hangers are secured and the base of the fan coil unit is leveled in both horizontal directions, taking into account the gradient for drainage flow as recommended in Figure A.
Page 21
Application Information Model: FWC-C The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable for piping and drainage and it must have a large distance between a door and unit.
Page 22
Application Information Model: FWC-FD The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable for piping and drainage and it must have a large distance between a door and unit.
Page 23
Application Information Model: FWC-H The indoor unit must be installed such that there is no short circuit of the cool discharge. Respect the installation clearance. Do not put the indoor unit where there is direct sunlight on unit. The location is suitable for piping and drainage and it must have a large distance between a door and unit.
Page 24
Application Information Model: FUD Mounting Ensure that the overhead supports are strong enough to hold the unit’s weight. Position hanger rods and check for alignment with the unit. Check that hangers are secure and that the base of fan-coil unit is level in the two horizontal directions, taking into account the gradient recommended for drainage flow as shown.
Page 25
Application Information Others The controller board of 4 pipes system (W3) comes with other dry contact options. Unoccupied Mode COMP Anti Freeze Mode Window Open Mode TRANSFORMER Unoccupied Mode If the dry contact is closed, the Unoccupied mode is activated and vice versa. When Timer On is active, system goes back to Occupied mode.
Sound Data Sound Data Sound Pressure Level 1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise Model Speed (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FWW02L High FWW03L High FWW04L High FWW05L High FWW06L Microphone position: 1m in front and 0.8m below the vertical centre line of the unit. 1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise Model...
Page 27
Sound Data 1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise Model Speed (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FWK06E(H) High FWK08E(H) High *FWK09E(H) High *FWK11E(H) High *FWK13E(H) Microphone position: 1.4m/*1.5m below the face center of the air return of the unit. 1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise Model...
Page 28
Sound Data 1/1 Octave A-Weighted Sound Pressure (dBA), ref 20µPa Overall Noise Model Speed (dBA) Criteria 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FWC03C High FWC04C High FWC06C High FWC07C High FWC09C High FWC12C High FWC14C High FWC16C Microphone position: 1.5m below the centre of the unit. (Tested with 2m length duct at the air discharge outlet and 1m length of air return duct).
Page 29
Sound Data 1/1 Octave Sound Pressure Level (dB, reference 20mPa) Overall Noise Model Speed Criteria 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA) High FWC02FD High FWC03FD High FWC04FD High FWC05FD High FWC06FD High FWC08FD High...
Page 30
Sound Data 1/1 Octave Sound Pressure Level (dB, reference 20mPa) Overall Noise Model Speed Criteria 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz (dBA) High FWC03H High FWC04H High FWC06H High FWC08H High FWC10H High FWC12H High...
Page 31
Sound Data Sound Power Level 1/1 Octave Sound Power Level (dB, reference 1pW) Overall Model Speed A (dBA) 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FWW02L High FWW03L High FWW04L High FWW05L High FWW06L Measured In Reverberation Chamber 1/1 Octave Sound Power Level (dB, reference 1pW) Overall Model Speed...
Sound Data 1/1 Octave Sound Power Level (dB, reference 1pW) Overall Model Speed A (dBA) 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FWKE05E(H) Quiet High FWKE08E(H) Quiet High FWKE11E(H) Quiet Measured In Reverberation Chamber 1/1 Octave Sound Power Level (dB, reference 1pW) Overall Model Speed...
Page 33
Sound Data 1/1 Octave Sound Power Level (dB, reference 1pW) Overall Model Speed A (dBA) 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FWC03C High FWC04C High FWC06C High FWC07C High FWC09C High FWC11C High FWC12C High FWC14C High FWC16C Measured In Reverberation Chamber...
Page 34
Sound Data 1/1 Octave Sound Power Level (dB, reference 1pW) Overall A Model Speed (dBA) 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz High FWC02FD High FWC03FD High FWC04FD High FWC05FD High FWC06FD High FWC08FD High FWC10FD Measured In Reverberation Chamber...
Page 35
Sound Data 1/1 Octave Sound Power Level (dB, reference 1pW) Overall Model Speed 125Hz 250Hz 500Hz 1kHz 2kHz 4kHz 8kHz (dBA) High FWC03H High FWC04H High FWC06H High FWC08H High FWC10H High FWC12H High FWC14H High FWC16H High FWC18H High FWC20H Microphone position: 1.5m below the centre of the unit.
Selection Process Selection Process Fan Performance Chart Example 1 : The following are the design requirements for FUD30B unit: Model: FUD30B Supply Air Quantity 4200 External Static Pressure Step 1: From the fan curve (at 4200 CFM), Standard operating system; Total Static Pressure Internal Static Pressure External Static Pressure...
Page 63
Selection Process The following table summarizes the pulley data, motor size used for the FUD series, as manufactured: Pulley Center V-Belt V-Belt Motor Blower Motor Motor Distance, C Length Length Pulley Pulley Size Speed Model Diameter Diameter Horizontal Vertical Horizontal Vertical FUD30B 1405...
Page 86
Selection Process FWC14H 0.48 0.44 HIGH 0.40 0.36 0.32 MEDIUM 0.28 0.24 0.20 0.16 0.12 LOWER LIMIT 0.08 1000 1200 1400 1600 1800 Air Flow 2059-010...
Page 87
Selection Process FWC16H 0.48 0.44 HIGH 0.40 0.36 0.32 MEDIUM 0.28 0.24 0.20 0.16 0.12 LOWER LIMIT 0.08 1000 1200 1400 1600 1800 2000 Air Flow 2059-011...
Page 88
Selection Process FWC18H 0.48 0.44 HIGH 0.40 0.36 0.32 MEDIUM 0.28 0.24 0.20 0.16 0.12 LOWER LIMIT 0.08 1000 1200 1400 1600 1800 2000 2200 23 25 60 62 Air Flow 2059-012...
Page 89
Selection Process FWC20H 0.48 0.44 HIGH 0.40 0.36 0.32 0.28 MEDIUM 0.24 0.20 0.16 0.12 0.08 0.04 LOWER LIMIT 0.00 1000 1200 1400 1600 1800 2000 2200 2400 23 25 Air Flow 2059-013...
Page 90
Selection Process FUD20B mmAq HIGH MEDIUM 1000 1500 2000 2500 3000 1000 1500 2000 2500 3000 3500 4000 4500 5100 Air Flow...
Page 91
Selection Process FUD25B mmAq MEDIUM HIGH 2000 2500 3000 3500 4000 3400 4000 4500 5000 5500 6000 6500 6800 Air Flow...
Page 92
Selection Process FUD30B 1.5 kW 1.1 kW Standard Point Internal Static Pressure with air filter Internal Static Pressure w/o air filter 3500 4000 4500 5000 1800 2000 1652 2200 2360 Air Flow...
Page 93
Selection Process FUD30B 1.5 kW 1.1 kW Standard Point Internal Static Pressure with air filter Internal Static Pressure w/o air filter 3500 4000 4500 5000 1800 2000 1652 2200 2360 Air Flow...
Engineering & Physical Data Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWW02L FWW03L FWW04L FWW05L FWW06L Btu/h 8300 9200 11300 15500 18000 NOMINAL COOLING CAPACITY 2430 2700 3310 4540 5280 Btu/h 6300 6900 9000 11700 14000 NOMINAL SENSIBLE COOLING CAPACITY...
Page 95
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWF02C FWF04C FWF05C Btu/h 8500 14000 15500 NOMINAL COOLING CAPACITY 2490 4100 4540 Btu/h 6500 10000 11500 NOMINAL SENSIBLE COOLING CAPACITY 1910 2930 3370 Btu/h 12000 16000 18000 NOMINAL HEATING CAPACITY (ENTERING WATER TEMP.
Page 96
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWK06E FWK08E FWK09E FWK11E FWK13E Btu/h 21000 25000 30000 38000 43000 NOMINAL COOLING CAPACITY 6150 7330 8790 11140 12600 Btu/h 16700 19200 22300 27400 31000 NOMINAL SENSIBLE COOLING CAPACITY 4890 5630 6540...
Page 97
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWK06EH FWK08EH FWK09EH FWK11EH FWK13EH Btu/h 16400 18500 24600 29600 31300 NOMINAL COOLING CAPACITY 4800 5430 7210 8670 9160 Btu/h 14487 16108 19922 23991 25790 NOMINAL SENSIBLE COOLING CAPACITY 4250 4720 5840...
Page 98
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit FWKE05E FWKE08E MODEL HIGH MEDIUM QUIET HIGH MEDIUM QUIET Btu/h 20100 15900 11900 8200 30000 24700 19800 15200 NOMINAL COOLING CAPACITY 5900 4650 3500 2400 8800 7250 5800 4550 Btu/h 15400...
Page 99
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit FWKE11E MODEL HIGH MEDIUM QUIET Btu/h 40100 33100 26800 21000 NOMINAL COOLING CAPACITY 11750 9700 7850 6150 Btu/h 28600 23800 18900 14600 NOMINAL SENSIBLE COOLING CAPACITY 8370 6970 5540 4270 Btu/h...
Page 100
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit FWKE05EH FWKE08EH MODEL HIGH MEDIUM QUIET HIGH MEDIUM QUIET Btu/h 15000 12300 9600 6800 24600 20800 17100 13300 NOMINAL COOLING CAPACITY 4400 3600 2800 2000 7200 6100 5000 3900 Btu/h 13100...
Page 101
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit FWKE11EH MODEL HIGH MEDIUM QUIET Btu/h 30700 26400 22200 17700 NOMINAL COOLING CAPACITY 9000 7750 6500 5200 Btu/h 24500 20700 16700 13300 NOMINAL SENSIBLE COOLING CAPACITY 7170 6060 4900 3890 Btu/h...
Page 102
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWE05E FWE06E FWE07E FWE08E FWE10E FWE12E Btu/h 15500 20300 21000 25000 34000 47000 NOMINAL COOLING CAPACITY 4540 5950 6150 7330 9960 13770 Btu/h 12700 15400 16150 19250 25500 32900 NOMINAL SENSIBLE COOLING CAPACITY...
Page 103
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWC03C FWC04C FWC06C FWC07C Btu/h 9900 11600 18000 22500 NOMINAL COOLING CAPACITY 2900 3400 5280 6590 Btu/h 7000 8120 12600 15750 NOMINAL SENSIBLE COOLING CAPACITY 2050 2380 3690 4620 Btu/h...
Page 104
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWC09C FWC11C FWC12C FWC14C FWC16C Btu/h 24800 38000 37000 44700 51800 NOMINAL COOLING CAPACITY 7270 11140 10840 13100 15180 Btu/h 19700 29800 29300 35100 40900 NOMINAL SENSIBLE COOLING CAPACITY 5770 8730 8590...
Page 105
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWC02FD FWC03FD FWC04FD FWC05FD Btu/h 6600 8700 12100 14000 NOMINAL COOLING CAPACITY 1930 2550 3550 4100 Btu/h 5400 6300 9500 9600 NOMINAL SENSIBLE COOLING CAPACITY 1580 1850 2780 2810 NOMINAL TOTAL INPUT POWER...
Page 106
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FWC06FD FWC08FD FWC10FD Btu/h 17000 24500 28500 NOMINAL COOLING CAPACITY 4980 7180 8350 Btu/h 11800 17000 20200 NOMINAL SENSIBLE COOLING CAPACITY 3460 4980 5920 NOMINAL TOTAL INPUT POWER NOMINAL RUNNING CURRENT 0.95 1.28...
Page 107
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit Medium Static Pressure MODEL FWC03H FWC04H FWC06H FWC08H FWC10H Btu/h 7900 10500 14800 21500 26000 NOMINAL COOLING CAPACITY 2320 3080 4340 6300 7620 Btu/h 6200 8400 11900 16900 19400 NOMINAL SENSIBLE COOLING CAPACITY 1820...
Page 108
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit Medium Static Pressure MODEL FWC12H FWC14H FWC16H FWC18H FWC20H Btu/h 29000 39500 44500 49500 52000 NOMINAL COOLING CAPACITY 8500 11580 13040 14510 15240 Btu/h 22200 32600 35900 40300 42700 NOMINAL SENSIBLE COOLING CAPACITY 6510...
Page 109
Engineering & Physical Data Engineering Data - Chilled Water Fan Coil Unit MODEL FUD20B FUD25B FUD30B FUD40B Btu/h 75600 95000 125000 150000 NOMINAL COOLING CAPACITY 22160 27840 36640 43960 Btu/h 53700 69400 90000 106500 NOMINAL SENSIBLE COOLING CAPACITY 15740 20340 26380 31210 Btu/h...
Outlines & Dimensions Outlines & Dimensions Indoor Unit Model: FWW02/03/04/05/06L THE MARK SHOWS PIPING DIRECTION LEFT RIGHT TOP VIEW NAME PLATE SIGNAL RECEIVER TERMINAL BLOCK WITH EARTH INDOOR UNIT TERMINAL ON/OFF SWITCH SIDE VIEW BOTTOM BOTTOM ROOM TEMPERATURE THERMISTOR (INSIDE) LOUVER FRONT GRILLE FIXED SCREWS (INSIDE)
Page 111
Outlines & Dimensions Model: FWW02/03/04/05/06L t a l (5 spots in all) Through the wall hole Ø 65mm Drain hose position Liquid pipe end Gas pipe end ALTERNATIVE INSTALLATION PLATE FWW02/03/04L Dimension Model 02/03/04 t a l (7 spots in all) Through the wall hole Ø...
Page 112
Outlines & Dimensions Model: FWF02/04/05C SEE DETAIL A DETAIL A Dimension Model 02/04/05 Note: Dimension in mm...
Page 113
Outlines & Dimensions Model: FWK06/08/09/11/13E(H) Dimension Model 06/08/09 11/13 Note: Dimension in mm...
Page 114
Outlines & Dimensions Model: FWKE05/08/11E(H) Dimension Model 05/08 Note: Dimension in mm...
Page 115
Outlines & Dimensions Model: FWE05/06/07E DRAIN PIPE WATER INLET WATER OUTLET DETAIL A SEE DETAIL A Dimension Model FWE05/06/07E 800 1090 230 Mounting Bracket Dimension Model 05/06/07 1073 Note: Dimension in mm...
Page 117
Outlines & Dimensions Model: FWC03C LEFT PIPING WATER OUTLET WATER INLET RIGHT PIPING WATER OUTLET WATER INLET Dimension Model 808 774 702 741 267 662 662 225 115 218 411 351 211 211 Note: Dimension in mm...
Page 118
Outlines & Dimensions Model: FWC04/06/07C LEFT PIPING DETAIL B FOR FWPMM6/7 DETAIL A FOR FWPMM4 WATER OUTLET WATER OUTLET WATER INLET WATER INLET SEE DETAIL A FOR FWPMM4 SEE DETAIL B FOR FWPMM6/7 WATER INLET WATER OUTLET RIGHT PIPING DETAIL A FOR FWPMM4 DETAIL B FOR FWPMM6/7 WATER OUTLET WATER OUTLET...
Page 119
Outlines & Dimensions Model: FWC08/11C LEFT PIPING WATER OUTLET WATER INLET RIGHT PIPING WATER INLET WATER OUTLET Dimension Model 1292 1297 1225 1264 1174 Dimension Model Note: Dimension in mm...
Page 120
Outlines & Dimensions Model: FWC09/12/14/16C LEFT PIPING WATER OUTLET WATER INLET RIGHT PIPING WATER INLET WATER OUTLET Dimension Model 1088 1105 1033 1072 1342 1358 1287 1326 1236 1542 1558 1487 1526 1436 Dimension Model Note: Dimension in mm...
Page 121
Outlines & Dimensions Model: FWC02/03/04/05/06/08/10FD LEFT PIPING RIGHT PIPING Dimension Model 02/03 04/05 1060 1390 1246 1207 1210 1271 1600 1456 1417 1420 1481 Note: Dimension in mm...
Page 122
Outlines & Dimensions Model: FWC03/04/06H Dimension Model 03/04 Note: Dimension in mm...
Page 123
Outlines & Dimensions Model: FWC08/10H Dimension Model 08/10 1289 1264 1048 1127 1103 Note: Dimension in mm...
Page 124
Outlines & Dimensions Model: FWC12H MOUNTING HOLE I� / (4 X 10.0 X 16.0) .!,[ � � CONDENSATE DRAIN (R3/4") �v � ""'" WATER OUT 3/4" BSPT FEMALE THREAD ADAPTOR � � � � � • WATER IN 3/4" BSPT FEMALE THREAD ADAPTOR Dimension Model 1540...
Wiring Diagrams Wiring Diagrams Model: FWW02/03/04/05/06L POWER SUPPLY 220-240V/1Ph/50Hz Model: FWF02/04/05C WIRED CONTROLLER (OPTIONAL) POWER SUPPLY 220-240V/1Ph/50Hz TO 2/3 WAY VALVE Note: Please do not install using third party controller as this will affect the functionality of unit feature...
Page 130
Wiring Diagrams Model: FWK06/08/09/11/13E TO 2/3 WAY VALVE POWER SUPPLY 220-240V/1Ph/50Hz WIRED CONTROLLER (OPTIONAL) Note: Please do not install using third party controller as this will affect the functionality of unit feature Model: FWK06/08/09/11/13EH TO 2/3 WAY VALVE TO 2/3 WAY VALVE (HEATING) (COOLING) POWER SUPPLY...
Page 131
Wiring Diagrams Model: FWKE05/08E WIRED CONTROLLER (OPTIONAL) POWER SUPPLY 220-240V/1Ph/50Hz TO 2/3 WAY VALVE Note: Please do not install using third party controller as this will affect the functionality of unit feature Model: FWKE11E WIRED CONTROLLER (OPTIONAL) POWER SUPPLY 220-240V/1Ph/50Hz TO 2/3 WAY VALVE Note: Please do not install using third party controller as this will affect the functionality of unit feature...
Page 132
Wiring Diagrams Model: FWKE05/08EH WIRED CONTROLLER (OPTIONAL) POWER SUPPLY 220-240V/1Ph/50Hz TO 2/3 WAY VALVE TO 2/3 WAY VALVE (HEATING) (COOLING) Note: Please do not install using third party controller as this will affect the functionality of unit feature Model: FWKE11EH WIRED CONTROLLER (OPTIONAL)
Page 133
Wiring Diagrams Model: FWE05/06/07E WIRED CONTROLLER (OPTIONAL) POWER SUPPLY 220-240V/1Ph/50Hz TO 2/3 WAY VALVE Model: FWE08/10/12E TO 2/3 WAY VALVE POWER SUPPLY 220-240V/1Ph/50Hz WIRED CONTROLLER (OPTIONAL) Note: Please do not install using third party controller as this will affect the functionality of unit feature...
Page 134
Wiring Diagrams Model: FWC03/04/06/07C (With Controller) WIRED CONTROLLER (OPTIONAL) POWER SUPPLY 220-240V/1Ph/50Hz TO 2/3 WAY VALVE Model: FWC09/11/12/14/16C (With Controller) WIRED CONTROLLER (OPTIONAL) POWER SUPPLY 220-240V/1Ph/50Hz TO 2/3 WAY VALVE...
Service & Maintenance Service & Maintenance Moving machinery and electrical power hazards. May cause severe personal injury or death. Disconnect from main power supply before servicing equipment. The unit is designed to give long life operation with minimum maintenance required. However, it should be regularly checked and the following items should be given due attention.