Daikin WGZ030DW Operating And Maintenance Manual page 40

Water-cooled scroll compressor chillers 30 to 200 tons, 105 to 700 kw r-410a 50-60 hertz
Table of Contents

Advertisement

8-Fan Remote Condenser, R22, R407C
Stage
1
2
3
4
8-Fan Remote Condenser, R410A
Stage
1
2
3
4
10 Fan Remote Condenser, R410A
Stage
1
2
3
4
5
12Fan Remote Condenser, R410A
Stage
1
2
3
4
5
6
Normal Operation – Staging Up
At startup, the first fan will start when the saturated condenser temperature rises above the target. After
this, the stage up deadbands apply.
When the saturated condenser temperature is above the Target + the active deadband, a Stage Up error is
accumulated.
Stage Up Error Step = Saturated Condenser Refrigerant temperature – (Target + Stage Up dead band)
The Stage Up Error Step is added the Stage Up Accumulator once every Stage Up Error Delay seconds.
When Stage Up Error Accumulator is greater than the Stage Up Error Set Point another stage is started.
When a stage up occurs or the saturated condenser temperature falls back within the Stage Up dead band
the Stage Up Accumulator is reset to zero.
Normal Operation – Staging Down
There are four Stage Down dead bands, one for each stage.
When the saturated condenser refrigerant temperature is below the condenser saturated temperature target
– the active dead band, a Stage Down error is accumulated.
Stage Down Error Step = (Target – Stage Down dead band) – Saturated Condenser Refrigerant
temperature
The Stage Down Error Step is added to Stage Down Accumulator once every Stage Down Error Delay
seconds. When the Stage Down Accumulator is greater than the Stage Down Error Set Point another stage
of condenser fans turn off. The last stage on will not shut off until the circuit is in an off state.
40
Fans Operating on Circuit 1
Fan 1
Fans 1, 3
Fans 1, 3, 5
Fans 1, 3, 5, 7
Fans Operating on Circuit 1
Fan 1
Fans 1, 3
Fans 1, 5, 7
Fans 1, 3, 5, 7
Fans Operating on Circuit 1
Fan 1
Fans 1, 3
Fans 1, 5, 7
Fans 1, 3, 5, 7
Fans 1, 3, 5, 7, 9
Fans Operating on Circuit 1
Fan 1
Fans 1, 3
Fans 1, 5, 7
Fans 1, 3, 5, 7
Fans 1, 3, 5, 7, 9
Fans 1, 3, 5, 7, 9, 11
WGZ030D through WGZ200D
Fans Operating on Circuit 2
Fan 2
Fans 2, 4
Fans 2, 6, 8
Fans 2, 4, 6, 8
Fans Operating on Circuit 2
Fan 2
Fans 2, 4
Fans 2, 6, 8
Fans 2, 4, 6, 8
Fans Operating on Circuit 2
Fan 2
Fans 2, 4
Fans 2, 6, 8
Fans 2, 4, 6, 8
Fans 2, 4, 6, 8, 10
Fans Operating on Circuit 2
Fan 2
Fans 2, 4
Fans 2, 6, 8
Fans 2, 4, 6, 8
Fans 2, 4, 6, 8, 10
Fans 2, 4, 6, 8, 10, 12
OMM 1130-2