Menu Screens - Daikin WGZ030DW Operating And Maintenance Manual

Water-cooled scroll compressor chillers 30 to 200 tons, 105 to 700 kw r-410a 50-60 hertz
Table of Contents

Advertisement

Figure 9, Display in the Shortcut (SCROLL) Mode and Keypad Layout
Air Conditioning
VIEW UNIT STATUS
Unit = COOL
Compr. #1/#2=OFF/OFF
Evap Pump = RUN
ENTER Key
Pressing the ENTER key changes the function of the ARROW keys to the editing function as shown
below:
LEFT key
Default, changes a value to the factory-set default value.
RIGHT key Cancel, cancels any change made to a value and returns to the original setting.
UP key
Increment, increases the value of the setting
DOWN key Decrement decreases the value of a setting.
These four edit functions are indicated by one-character abbreviation on the right side of the display (this
mode is entered by pressing the ENTER key).
Most menus containing setpoint values have several different setpoints shown on one menu. When in a
setpoint menu, the ENTER key is used to proceed from the top line to the second line and on downward.
The cursor will blink at the entry point for making a change. The ARROW keys (now in the edit mode)
are used to change the setpoint as described above. When the change has been made, press the ENTER
key to enter it. Nothing is changed until the ENTER key is pressed.
For example, to change the chilled water setpoint:
1. Press MENU key to go to the MENU mode.
2. Press SET (the UP Key) to go to the setpoint menus.
3. Press UNIT SPs (the Right key) to go to setpoints associated with unit operation.
4. Press the DOWN key to scroll down through the setpoint menus to the third menu which contains
Evap LWT=XX.X°F.
5. Press the ENTER key to move the cursor down from the top line to the second line in order to make
the change.
6. Use the ARROW keys (now in the edit mode as shown above) to change the setting.
7. When the desired value is achieved, press ENTER to enter it and also move the cursor down.
At this point, the following actions can be taken:
1. Change another setpoint in this menu by scrolling to it with the ENTER key.
2. Using the ENTER key, scroll to the first line in the menu. From there the ARROW keys can be used
to scroll to different menus.

Menu Screens

Various menus are shown in the controller display. Each menu screen shows specific information, in
some cases menus are only to view status of the unit, in some cases for checking alarms, and in some
cases they are used to set setpoint values that can be changed.
The menus are arranged in a matrix of screens across a top horizontal row. Some of these top-level
screens have sub-screens located under them. The content of each screen and its location in the matrix
are shown in Figure 10. A description of each menu begins on page 53.
The arrow keys on the controller are used to navigate through the menus. The keys are also used to
change numerical setpoint values contained in certain menus.
52
ARROW
WGZ030D through WGZ200D
MENU Key
ENTER Key
OMM 1130-2

Hide quick links:

Advertisement

Table of Contents
loading