Setpoints - Daikin WGZ030DW Operating And Maintenance Manual

Water-cooled scroll compressor chillers 30 to 200 tons, 105 to 700 kw r-410a 50-60 hertz
Table of Contents

Advertisement

Setpoints

The following parameters are remembered during power off, are factory set to the Default value, and can be
adjusted to any value in the Range column.
The PW (password) column indicates the password level that must be active in order to change the setpoint.
Passwords are as follows:
O = Operator [0100]
Table 7, Setpoints (setpoints with
Description
Unit Enable
*Unit Mode (R22, R407C, R410A
Unit Mode (R134a)
Control source
*Available Modes (R22,R407C,R410A)
*Available Modes (R134a)
Evap LWT
Ice LWT
Heat LWT (R134a only)
Evap Delta T
Startup Delta T
Stop Delta T
Max Pulldown Rate
Evap Recirculate Timer
Evap Pump
(Refrigerant = R410a,R134a)
Cond Delta T (R134a only)
Cond Pump Recirculate Timer
(Water-cooled = Yes)
Cond Pump
(Water-cooled=Yes & Ref=R410A or R134a
Low Ambient Lockout(Water-Cooled = No)
Demand Limit
* Water Cooled
Ice Time Delay
Clear Ice Delay
Hot Gas Delay Time
BAS Protocol
Ident number
Baud rate
Units
Language
* Refrigerant Select
Cooling Reset Type
Cooling Maximum Reset
Cooling Start Reset Delta T
Compressor
# of Compressors
(Refrig = R410A or R134a to select 6)
Clear Cycle Tmr
Stage Up Delay
Stage Down Delay
Start-Start
Stop-Start
OMM 1130-2
M = Manager [2001]
* are set at Daikin Applied factory)
Default
Off
Cool
Cool
Switches
Cool
Test, Cool, Cool w/Glycol, Cool/Heat, COOL/HEAT
Cool
Without Glycol: 40.0 to 60.0°F
44. 0 °F
With Glycol: 20.0 to 60.0°F (R22,R407C)
40. 0 °F
110.o°F
10.0 °F
10.0 °F
0.5 °F
1.0 °F
30
#1 Only
20.0°F
30
#1 Only
35.0 °F
Off
Off
12 hrs
No
30 sec.
Modbus
001
9600
F/psi
English
None
None
10 ºF
10 ºF
4
Off
240 sec
30
15 min
5 min
Range
Off, On
Cool, Cool w/Glycol, Ice w/Glycol, Test
Cool, Cool w/Glycol, Heat, Test
Keypad, Network, Switches
Cool, Cool w/Glycol, Cool/Ice w/Glycol
Ice w/Glycol, Test
w/Glycol, Heat w/Glycol,
40.0 to 85.0°F (R134a Only)
10.0 to 60.0°F (R410A)
20.0 to 85.0°F (R134a)
15.0 to 40.0 °F
110 to 165°F
6.0 to 16.0 °F
1.0 to 15.0 °F
0 to 3.0 °F
0.5 to 5.0 °F
15 to 300 seconds
#1 Only, #2 Only, Auto, #1 Prim,
#2 Prim
5.0 to 40.0°F
15 to 90 seconds
#1 Only, #2 Only, Auto, #1 Prim, #2 Prim
35 to 70 °F
If Speedtrol = Yes
-2.0 to70.0°F (R22,R407C)
-10.0 to 70.0 (R410A)
N/A (R134a)
Off, On
Off, On
1 to 23 hrs
No, Yes
30 to 180 seconds
BACnet, LonWorks, Modbus
000-200
1200,2400,4800,9600,19200
F/psi (only)
English (only)
R22, R407C, R410A, R134a
None, 4-20mA, [Return( Refrig = R134a only)]
0 to 16 ºF
0 to 16 ºF (Refrig = R134a only)
4, 6
On/Off
90 to 480 seconds
20 to 60 sec
10 to 60 min
3 to 20 min
PW
O
O
O
M
M
O
O
O
O
O
O
M
M
M
M
M
M
M
M
M
M
M
M
M
M
O
O
O
M
M
M
M
M
M
21