Bas Interface - Daikin WGZ030DW Operating And Maintenance Manual

Water-cooled scroll compressor chillers 30 to 200 tons, 105 to 700 kw r-410a 50-60 hertz
Table of Contents

Advertisement

BAS Interface

The BAS interface will use the supervisor port on the controller as a connection point.
Protocols Supported
The following building automation system (BAS) protocols are supported. It is possible to change the
building automation interface without loading different software.
BACnet®
When protocol is set to BACnet, the baud rate and ident set points are not accessible. The ident setting is
locked at 1 for BACnet, and the baud rate is locked to 19200.
LONworks®
With protocol set to LON, the baud rate and ident set points are not accessible. The ident setting is locked
at 1 for LON, and the baud rate is locked to 4800.
Modbus®
With the protocol set to Modbus, the baud rate and ident set points are accessible.
Available Parameters
Types: A = Analog, I= Integer, D= Digital
I/O: I = Input only, O = Output only , I/O = Input/Output
Type
Index
I/O
A
1
I/O
A
2
O
A
3
I/O
A
6
O
A
7
O
A
10
O
A
11
I
A
15
O
A
16
O
A
17
O
A
20
O
A
21
O
A
39
O
A
42
O
A
50
I/O
I
1
O
I
2
O
I
3
O
I
4
O
I
5
O
I
6
O
I
7
O
I
8
O
I
9
O
I
10
O
Continued next page.
72
Description
Network Cool LWT set point
Active LWT set point
Network limit set point
Evap LWT
Cond EWT
Unit capacity (%)
Network Cool LWT set point default
Suction temp
Evap sat temp
Evap pressure
Cond sat temp
Cond pressure
OAT
Active Capacity Limit
Network Ice LWT set point
Active alarms 1
Active alarms 2
Active alarms 3
Active alarms 4
Active alarms 5
Active alarms 6
Active alarms 7
Active alarms 8
Active alarms 9
Active alarms 10
WGZ030D through WGZ200D
L
W
BACnet
Modbus
ON
ORKS
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
OMM 1130-2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents