Daikin WGZ030DW Operating And Maintenance Manual page 5

Water-cooled scroll compressor chillers 30 to 200 tons, 105 to 700 kw r-410a 50-60 hertz
Table of Contents

Advertisement

Figure 2, Condenser Pressure Drop, WGZ030D – WGZ200D
Flow Rate (GPM)
Ref
Unit Model
#
A
WGZ030D
B
WGZ035D
C
WGZ040D
D
WGZ045D
E
WGZ050D
F
WGZ055D
G
WGZ060D
H
WGZ070D
I
WGZ080D
J
WGZ090D
K
WGZ100D
L
WGZ115D
M
WGZ130D
N
WGZ150D
O
WGZ170D
P
WGZ200D
OMM 1130-2
Min. Flow & PD
IP
SI
GPM
Ft.
L/S
kPa
56.1
2.4
3.5
7.2
64.9
3.4
4.1
10.2
76.3
2.7
4.8
8.1
85.3
3.6
5.4
10.8
96.4
2.9
6.1
8.7
105.8
3.8
6.7
11.4
113.4
4.5
7.2
13.5
132.8
4.1
8.4
12.3
146.8
3.7
9.3
11.1
165.0
3.4
10.4
10.2
183.4
3.4
11.6
10.2
211.7
4.8
13.4
14.3
235.1
6.1
14.8
18.2
274.9
6.2
17.3
18.5
317.4
5.5
20.0
16.4
352.7
7.4
22.3
22.1
Nom. Flow & PD
IP
SI
GPM
Ft.
L/S
kPa
89.7
6.3
5.7
18.8
103.8
8.6
6.5
25.7
122.1
6.9
7.7
20.6
136.5
9.2
8.6
27.5
154.2
7.5
9.7
22.4
169.2
9.7
10.7
29.0
181.5
11.6
11.5
34.7
212.4
10.4
13.4
31.1
234.9
9.5
14.8
28.4
264
8.8
16.7
26.3
293.4
8.8
18.5
26.3
338.7
12.3
21.4
36.8
376.2
15.5
23.7
46.3
439.8
15.8
27.7
47.2
507.9
14.0
32.0
41.8
564.3
18.8
35.6
56.2
Max. Flow & PD
IP
SI
GPM
Ft.
L/S
kPa
149.5
17.4
9.4
52.0
173.0
23.9
10.9
71.4
203.5
19.3
12.8
57.7
227.5
25.7
14.4
76.8
257.0
20.7
16.2
61.9
282.0
26.8
17.8
80.1
302.5
32.3
19.1
96.5
354.0
29.0
22.3
86.7
391.5
26.5
24.7
79.2
440.0
24.5
27.8
73.2
489.0
24.4
30.9
72.9
564.5
34.1
35.6
101.9
627.0
43.1
39.6
128.8
733.0
43.8
46.2
130.9
846.5
38.9
53.4
116.3
940.5
52.3
59.3
156.3
5