Daikin WGZ030DW Operating And Maintenance Manual page 54

Water-cooled scroll compressor chillers 30 to 200 tons, 105 to 700 kw r-410a 50-60 hertz
Table of Contents

Advertisement

VIEW menu:
VIEW
<
<
<
<
VIEW UNIT menu:
VIEW
UNIT
SET menu:
SET <
ALARM LIMITS
<
< COMPRESSOR SPs
< FANS/TOWER SPs
Screen Definitions – VIEW
View Unit Status
VIEW UNIT STATUS (1)
Auto
Cooling Stage = 0
Evap Pump = RUN
Unit states can be OFF, COOL, GYLCOL, ICE, or ALARM as determined from the Unit Mode setpoint,
the Unit Enable, and the presence of an alarm.
Circuit states can be OFF/OFF, ON/OFF, OFF/ON, and ON/ON.
Evaporator Pump States can be OFF, STRT, or RUN.
When more than one screen are stacked (i.e., relate to each other on the same subject), they are numbered
sequentially with the numbers appearing in the upper-right corner.
VIEW UNIT STATUS (2)
Demand Limit=Stg 4
Network Limit=Stg 4
VIEW UNIT STATUS (3)
Stg Up Delay=XXX sec
Stg Dn Delay=XXX sec
Ice Delay=XXh
VIEW UNIT STATUS (4)
D.O.
111111111
123456789012345678
000000000000000000
This menu gives the status of digital outputs (D.O.), 1=ON, 0=OFF. Numbers are 1 through 18. See
Table 6 on page 19 for number reference.
VIEW UNIT STATUS (5)
D.I.
111111111
123456789012345678
000000000000000000
54
COMPRESSOR
UNIT
EVAPORATOR
FANS/TOWER
<
TEMP
<
STATUS
< REFRIGERANT
UNIT SPs
XXm
WGZ030D through WGZ200D
OMM 1130-2