Daikin WGZ030DW Operating And Maintenance Manual page 64

Water-cooled scroll compressor chillers 30 to 200 tons, 105 to 700 kw r-410a 50-60 hertz
Table of Contents

Advertisement

# of Compressors = 4
SET COMP SPs
Comp 1 = Enable
Comp 3 = Enable
# of Compressors = 4
SET COMP SPs
Comp 2 = Enable
Comp 4 = Enable
Enable screens #3 and #4 require the manager password to change.
SET COMP SPs
Expansion Valve
Type = Thermal
Expansion Valve Type = Electronic
SET COMP SPs
Cir 1 EXV
EXV Control = Auto
Manual EXV Pos=XXX.X
Expansion Valve Type = Electronic
SET COMP SPs
Cir 2 EXV
EXV Control = Auto
Manual EXV Pos=XXX.X
Expansion Valve Type = Electronic Only
SET COMP SPs (8)
SuperheatTarg= XX.X
SET ALARM LIMITS
SET ALARM LMTS
Low EVAP Pressure
Hold=XXXpsi
Unload=XXXpsi
The Hold and Unload have the same default value of 59 psi. If two compressors are running, the
LowEvPrUnld is in effect and the lag compressor will be shut off to unload the unit. If one compressor is
running, the LowEvPrHold is in effect and the lag compressor is prevented from starting, thereby holding
the unit capacity.
64
# of Compressors = 6
(3)
SET COMP SPs
Comp 1 = Enable
Comp 3 = Enable
Comp 5 = Enable
# of Compressors = 6
(4)
SET COMP SPs
Comp 2 = Enable
Comp 4 = Enable
Comp 6 = Enable
TGZ Units Only (R134a)
(5)
SET COMP SPs
Expansion Valve
Type = Electronic
MaxOpPress=XXX.X psi
(6)
(7)
(1)
WGZ030D through WGZ200D
(3)
(4)
(5)
OMM 1130-2