Inverter and peripheral devices
1.2.1

Peripheral devices

Check the motor capacity of the inverter you purchased. Appropriate peripheral devices must be selected according to
the capacity. Refer to the following list and prepare appropriate peripheral devices:
200V class
Motor Output
Applicable Inverter Type
(kW(HP))
*1
0.4 (1/2)
FR-A720-00030-NA/N4
0.75 (1)
FR-A720-00050-NA/N4
1.5 (2)
FR-A720-00080-NA/N4
2.2 (3)
FR-A720-00110-NA/N4
3.7 (5)
FR-A720-00175-NA/N4
5.5 (7.5)
FR-A720-00240-NA/N4
7.5 (10)
FR-A720-00330-NA/N4
11 (15)
FR-A720-00460-NA
15 (20)
FR-A720-00610-NA
18.5 (25)
FR-A720-00760-NA
22 (30)
FR-A720-00900-NA
30 (40)
FR-A720-01150-NA
37 (50)
FR-A720-01450-NA
45 (60)
FR-A720-01750-NA
55 (75)
FR-A720-02150-NA
75 (100)
FR-A720-02880-NA
90 (125)
FR-A720-03460-NA
*1
Selections for use of the Mitsubishi 4-pole standard motor with power supply voltage of 200VAC 50Hz.
*2
Select the MCCB according to the inverter power supply capacity.
Install one MCCB per inverter.
For installations in the United States or Canada, use the fuse certified by the UL and cUL.
(Refer to
Installation Guideline.)
*3
Magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic
contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC
with class AC-3 rated current for the motor rated current.
*4
When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts of the inverter, etc. Identify
the cause of the trip, then remove the cause and power on the breaker.
4
Breaker Selection
Reactor connection
without
30AF 5A
30AF 5A
30AF 10A
30AF 10A
30AF 15A
30AF 15A
30AF 20A
30AF 15A
30AF 30A
30AF 30A
50AF 50A
50AF 40A
100AF 60A
50AF 50A
100AF 75A
100AF 75A
225AF 125A
100AF 100A
225AF 150A
225AF 125A
225AF 175A
225AF 150A
225AF 225A
225AF 175A
400AF 250A
225AF 225A
400AF 300A
400AF 300A
400AF 400A
400AF 350A
400AF 400A
400AF 400A
Input Side Magnetic Contactor
*2,4
Reactor connection
with
without
S-N10
S-N10
S-N10
S-N10
S-N20, N21
S-N25
S-N25
S-N35
S-N50
S-N65
S-N80
S-N95
S-N150
S-N180
S-N220
*3
with
S-N10
S-N10
S-N10
S-N10
S-N10
S-N20, N21
S-N25
S-N35
S-N50
S-N50
S-N65
S-N80
S-N125
S-N150
S-N180
S-N300
S-N300
MCCB
INV
IM
MCCB
INV
IM