Mitsubishi Electric FR-A700 Instruction Manual page 293

Fr-a700 series to 03460-na/09620-na/00330-n4/00170-n4
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

⋅ Refer to the following table and set Pr. 73 and Pr. 267. (
Pr. 73
Terminal 2
Setting
Input
0
0 to 10V
1
0 to to 5V
(initial value)
2
0 to 10V
3
0 to 5V
4
0 to 10V
5
0 to 5V
6
0 to 20mA
7
0 to 20mA
10
0 to 10V
11
0 to 5V
12
0 to 10V
13
0 to 5V
14
0 to 10V
15
0 to 5V
16
0 to 20mA
17
0 to 20mA
0
1 (initial
value)
2
3
4
0 to 10V
5
0 to 5V
6
7
10
11
12
13
14
0 to 10V
15
0 to 5V
16
17
⋅ Set the voltage/current input switch referring to the table below.
Terminal 2 Input
Specifications
Voltage input (0 to 10V)
0, 2, 4, 10, 12, 14
Voltage input (0 to 5V)
1 (initial value), 3, 5, 11, 13, 15
Current input (0 to 20mA)
6, 7, 16, 17
indicates an initial value.
CAUTION
⋅ Turn the AU signal on to make terminal 4 valid.
⋅ Match the setting of parameter and switch. A different setting may cause a fault, failure or malfunction.
⋅ The terminal 1 (frequency setting auxiliary input) signal is added to the main speed setting signal of the terminal 2 or 4.
⋅ When an override is selected, the terminal 1 or 4 is used for the main speed setting and the terminal 2 for the override signal
(50% to 150% at 0 to 5V or 0 to 10V). (When the main speed of the terminal 1 or terminal 4 is not input, compensation by the
terminal 2 is made invalid.))
⋅ Use Pr. 125 (Pr. 126) (frequency setting gain) to change the maximum output frequency at input of the maximum output frequency
command voltage (current). At this time, the command voltage (current) need not be input.
Also, the acceleration/deceleration time, which is a slope up/down to the acceleration/deceleration reference frequency, is not
affected by the change in Pr. 73 setting.
⋅ When Pr. 858 Terminal 4 function assignment, Pr. 868 Terminal 1 function assignment = "4", the value of the terminal 1 or terminal 4 is as
set to the stall prevention operation level. When terminal 1 and terminal 4 are used for frequency setting, set "0" (initial value) in Pr.
858 and Pr. 868.
Terminal 4 Input
Terminal 1
AU
Input
signal
0 to ±10V
0 to ±10V
0 to ±5V
0 to ±5V
0 to ±10V
0 to ±5V
0 to ±10V
0 to ±5V
Off
0 to ±10V
0 to ±10V
0 to ±5V
0 to ±5V
0 to ±10V
0 to ±5V
0 to ±10V
0 to ±5V
0 to ±10V
0 to ±10V
0 to ±5V
0 to ±5V
According to
Pr. 267 setting
0 to ±10V
0: 4 to 20mA
0 to ±5V
On
(initial value)
0 to ±10V
1: 0 to 5V
0 to ±10V
2: 0 to 10V
0 to ±5V
0 to ±5V
0 to ±10V
0 to ±5V
Pr. 73 Setting
Switch 2
OFF
OFF
ON
Frequency/torque setting by analog
indicates the main speed setting)
Compensation Input
Pr. 73
Terminal and
Setting
Compensation
0
1
Terminal 1
(initial value)
Added compensation
2
3
4
Terminal 2
5
6
7
10
Terminal 1
Added compensation
11
12
13
14
Terminal 2
15
16
Terminal 1
17
Added compensation
0
1
Terminal 1
(initial value)
Added compensation
2
3
4
Terminal 2
5
6
7
10
Terminal 1
Added compensation
11
12
13
14
Terminal 2
15
16
Terminal 1
17
Added compensation
Terminal 4 Input
Specifications
Voltage input (0 to 10V)
2
Voltage input (0 to 5V)
1
Current input (4 to 20mA)
0 (initial value)
input (terminal 1, 2, 4)
Polarity
Reversible
Method
No
(Indicates that
a frequency
command
signal of
negative
Override
polarity is not
accepted.)
Yes
Override
No
(Indicates that
a frequency
command
signal of
negative
Override
polarity is not
accepted.)
Yes
Override
⎯ : Invaild
Pr. 267 Setting
Switch 1
OFF
OFF
ON
283
4

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a720-00030Fr-a740-00015

Table of Contents