Mitsubishi Electric FR-A700 Instruction Manual page 182

Fr-a700 series to 03460-na/09620-na/00330-n4/00170-n4
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Frequency setting by external terminals
REMARKS
During jog operation or PID control operation, the remote setting function is invalid.
Setting frequency is "0"
⋅ Even when the remotely-set
frequency is cleared by turning
on the RL (clear) signal after
turn off (on) of both the RH and
RM signals, the inverter
operates at the remotely-set
frequency stored in the last
operation if power is reapplied
before one minute has elapsed
since turn off (on) of both the
RH and RM signals
⋅ When the remotely-set
frequency is cleared by turning
on the RL (clear) signal after
turn off (on) of both the RH and
RM signals, the inverter
operates at the frequency in the
remotely-set frequency cleared
state if power is reapplied after
one minute has elapsed since
turn off (on) of both the RH and
RM signals.
When selecting this function, re-set the maximum frequency according to the machine.
♦ Parameters referred to ♦
Pr. 1 Maximum frequency, Pr. 18 High speed maximum frequency
Pr. 7 Acceleration time, Pr. 8 Deceleration time, Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time
Pr. 28 Multi-speed input compensation selection
Pr. 178 to Pr. 189 (input terminal function selection)
172
Remotely-set frequency stored last time
Acceleration (RH)
ON
Deceleration (RM) OFF
Clear (RL)
Forward rotation
(STF)
Power supply
Remotely-set frequency stored last time
Acceleration (RH)
Deceleration (RM) OFF
Clear (RL)
Forward rotation (STF)
Power supply
CAUTION
Refer to page 157
Refer to page 170
Refer to page 228
Within 1 minute
Remotely-set frequency stored last time
ON
ON
ON
ON
ON
One minute
More than
one minute
Operation is performed at the set
frequency 0Hz.
ON
ON
ON
ON
ON
Time
Time
ON
Refer to page 173