Frequency/torque setting by analog
input (terminal 1, 2, 4)

4.21.7 4mA input check of current input (Pr. 573)

When inputting 4 to 20mA current to terminal 2 or terminal 4, decrease in analog current input is detected to
enable continuous operation even if input has decreased.
Parameter
Name
Number
573
4mA input check selection
Set frequency
60Hz
Current input
decrease detection
*
2mA
4mA
Normal use range
* When Pr. 573 = "1", input decrease is detected (LF signal output) even if
the analog input value to bias frequency of terminal 2 or terminal 4 is set
to 2mA or less using C2 (Pr. 902) or C5 (Pr. 904) and the value is not as
bias frequency settings.
During external operation (Pr. 573 = 1)
Output frequency
Analog input
20mA
4mA
STF
LF signal
During PID control (reverse action) (Pr. 573 = 1)
Output frequency
20mA
4mA
STF
LF signal
PID signal
CAUTION
· When terminal assignment is changed using Pr. 190 to Pr. 196 (output terminal function selection), the other functions may be
affected. Please make setting after confirming the function of each terminal.
300
Initial Value
9999
When C3 (C6) = 0%
20mA
Analog input
Set point (fixed)
Measured value
Setting
Range
When the current input drops to or below 2mA,
the LF signal is output and inverter continues
1
operation at the frequency (average value) just
before current reaches 2mA.
9999
4mA input is not checked.
(1) Operation at a current input decrease
continues (Pr. 573 = "1")
⋅ When the input current of terminal 4 (terminal 2) falls
2mA or below, output minor fault signal (LF) is output.
⋅ When the current falls below 2mA, the output frequency
(average value) before detection is retained and
operation at the retained frequency continues.
⋅ When the current input increases above 3mA, the
LF signal output is turned off and the inverter
operates according to the current input.
⋅ For the LF signal, set "98 (positive logic) or 198
(negative logic)" in Pr. 190 to Pr. 196 (output terminal
function selection) and assign functions to the output
terminal.
⋅ Since turning off the start command clears the
retained frequency, the inverter does not operate at
the retained frequency even if restarted.
Operation
continue
Return
Input current
decrease
3mA
2mA
Operation
continue
Input current
decrease
Return
3mA
2mA
On during input decrease
Description
Time
Time