Mitsubishi Electric FR-A700 Instruction Manual page 304

Fr-a700 series to 03460-na/09620-na/00330-n4/00170-n4
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Frequency/torque setting by analog
input (terminal 1, 2, 4)
(c) Method to adjust only the frequency without adjustment of a gain voltage (current).
(When changing the gain frequency from 60Hz to 50Hz)
Operation
1.
(Pr. 126) appears.
2.
Press
to show the currently set value.
(60.00Hz)
3.
Turn
to change the set value to
"
". (50.00Hz)
4.
Press
to set.
5.
Mode/monitor check
Press
twice to choose the
monitor/frequency monitor.
6.
Apply a voltage across the inverter
terminals 2-5 (across 4-5) and turn on the
start command (STF, STR).
Operation starts at 50Hz.
REMARKS
⋅ Changing C4 (Pr. 903) or C7 (Pr. 905) (gain adjustment) value will not change the Pr. 20 value. The input of terminal 1 (frequency
setting auxiliary input) is added to the frequency setting signal.
⋅ For the operation procedure using the parameter unit (FR-PU04/FR-PU07), refer to the FR-PU04/FR-PU07 instruction manual.
⋅ When setting the value to 120Hz or more, it is necessary to set Pr. 18 High speed maximum frequency to 120Hz or more. (Refer to
page 157)
⋅ Make the bias frequency setting using calibration parameter C2 (Pr. 902) or C5 (Pr. 904). (Refer to page 291)
Take care when setting any value other than "0" as the bias speed at 0V (0mA). Even if a frequency command is
not given, merely turning on the start signal will start the motor at the preset frequency.
♦ Parameters referred to ♦
Pr. 20 Acceleration/deceleration reference frequency
Pr. 73 Analog input selection, Pr. 267 Terminal 4 input selection
Pr. 79 Operation mode selection
294
Pr. 125) or
Flicker...Parameter setting complete!!
CAUTION
Refer to page 173
Refer to page 282
Refer to page 308
Display
or
Terminal 2 input
Terminal 4 input
Terminal 2 input
Terminal 4 input

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a720-00030Fr-a740-00015

Table of Contents