Mitsubishi Electric FR-A700 Instruction Manual page 75

Fr-a700 series to 03460-na/09620-na/00330-n4/00170-n4
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

(14) If the machine must not be restarted when power is restored after a power failure, provide a magnetic contactor in the
inverter's input side and also make up a sequence which will not switch on the start signal.
If the start signal (start switch) remains on after a power failure, the inverter will automatically restart as soon as the
power is restored.
(15) Instructions for overload operation
When performing an operation of frequent start/stop with the inverter, rise/fall in the temperature of the transistor element
of the inverter will repeat due to a continuous flow of large current, shortening the life from thermal fatigue. Since thermal
fatigue is related to the amount of current, the life can be increased by reducing current at locked condition, starting
current, etc. Decreasing current may increase the life. However, decreasing current will result in insufficient torque and
the inverter may not start. Therefore, choose the inverter which has enough allowance for current (up to 2 rank larger in
capacity).
(16) Make sure that the specifications and rating match the system requirements.
(17) A motor with encoder is necessary for vector control. In addition, connect the encoder directly to the backlash-free motor
shaft. (An encoder is not necessary for real sensorless vector control.)
Precautions for use of the inverter
3
65

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a720-00030Fr-a740-00015

Table of Contents