4.21.4 Response level of analog input and noise elimination
(Pr. 74, Pr. 822, Pr. 826, Pr. 832, Pr. 836, Pr. 849)
Response level and stability of frequency reference command and torque reference command by analog input
(terminal 1, 2, 4) signal can be adjusted.
Parameter
Name
Number
74
Input filter time constant
822
Speed setting filter 1
826
Torque setting filter 1
832
Speed setting filter 2
836
Torque setting filter 2
Analog input offset
849
adjustment
(1) Block diagram
Terminal 1 (2, 4 ) input
Initial
Setting
Value
Range
The primary delay filter time constant for the analog input
1
0 to 8
can be set. A larger setting results in slower response.
Set the time constant of the primary delay filter relative to
0 to 5s
the external speed command (analog input command).
9999
9999
Pr. 74 used
Set the time constant of the primary delay filter relative to
0 to 5s
the external torque command (analog input command).
9999
9999
Pr. 74 used
9999
0 to 5s, 9999
Second function of Pr. 822 (valid when RT terminal is on)
9999
0 to 5s, 9999
Second function of Pr. 826 (valid when RT terminal is on)
This function provides speed command by analog input
100%
0 to 200%
(terminal 2) with offset. Motor rotation due to noise, etc.
by analog input can be avoided at zero speed command.
RT-OFF
Pr. 822 = 9999
Pr. 822
9999
Pr. 826 = 9999
Pr. 826 9999
Pr. 832 = 9999
RT-ON
Pr. 832 9999
Pr. 836 = 9999
Pr. 836 9999
Frequency/torque setting by analog
input (terminal 1, 2, 4)
Description
Pr. 74
Speed command
Pr. 822
Pr. 74
Torque command
Pr. 826
Pr. 832
Pr. 836
4