De Dietrich Gas 310/610 ECO
15.4.7 Cleaning the condensate collector
Clean the condensate collector by removing the inspection cover (next to the flue gas discharge) and then rinsing
the collector with water
Fig. 34 – Condensate collector inspection
15.4.8 Cleaning the siphon
Remove the complete siphon (located underneath condensate collector beneath the flue connection).
Remove siphon, clean and refill with clean water and re-fit.
Fig. 35 – Condensate siphon assembly
15.4.9 Cleaning/Replacing the Ignition/Ionization electrode
Remove safety bracket from the heat exchanger then remove the two retaining screws on the electrode
assembly, remove assembly and examine for wear and
dirt, clean and re-gap electrode 1/8" [3mm] re-fit if in good
condition (replace gasket if necessary).
Replace electrode assembly if necessary – then discard
screws and gasket and fit replacement assembly c/w new
gasket and screws making sure that the earth connection is
in good condition and in contact with the base plate and re-
fit safety bracket.
Fig. 36 – Ignition/ionization electrode
64