4.5 GAS 610 QUOTATION SPECIFICATION:

Fully assembled cast aluminum floor
standing sectional hot water boiler.
Premix burner with stainless steel
cylinder with perforated holes for precise
air-fuel mixture and velocity with a
stainless tube with woven steel fiber for
stable flame and heat insulation.
Fully condensing boiler.
ASME approved design, CRN for each
Canadian Province.
Precise air to fuel ratio through firing
range with high turn down 5:1 per unit.
Boiler comes complete with a digital
combination flame safe guard and a
boiler control, with comprehensive
operating, service and fault diagnostic
capabilities.
Firing capabilities, ON-Off, 2-stage or
fully modulating [0-10v].
Capable of BMS control.
Local-remote control [enable/disable].
Boiler control equipment communication
socket for PC or PDA device used with
OEM software for advanced service and
trouble-shooting diagnostics.
2 control orientation versions, service or
short end option.
4.6 Delivery & ordering options:
Available in 4 models
2, 4 stage or modulating control
Weather compensator control
Condensate neutralization system with or
without pump
Multiple boiler control
pressure switch
Gas valve proofing system
Low water cut-off control (CSD-1 compliant)
Safety relief valve according to system pressure
Combustion air filter
Cleaning tool
Accessories must be ordered in pairs, one for each module.
Consult factory DDR Americas Inc. [De Dietrich Boilers] for other available options, all orders must specify
if optional controls are to be installed or shipped loose.
De Dietrich Gas 310/610 ECO
Available for conventional chimney,
direct vent and sealed combustion
venting systems.
Fully factory pressure and fire tested.
Distinctive powder coasted enamel steel
removable casing.
Rigid steel boiler frame with castors for
easy maneuvering into boiler's final
position.
Certified by CSA for USA and Canadian
markets.
High combustion and thermal
efficiencies.
No proven water flow requirements.
No minimum temperature requirements.
Manufactured in an ISO 9001 certified
facility.
Max 100 psi - System water operating
pressure
ASME safety relief valve (x2)
Pressure & Temperature gauge (x2)
Optional communication protocol
gateway (LonWorks®, BACnet®, etc...)
Lead/lag (cascade) system manager for
up to 8 boilers, space heating pump, 2
mixing valve circuits, 2 mixing valve
pumps, DHW pump.
DHW production kit
Standard vent damper
Pressure transducer for system pressure
Low gas pressure switch
High gas pressure switch