Gas 310 Temperature based 68 – 194°F [20-90°C]
Set the value of the boiler control operation parameter to . To set the ratio between voltage and the
desired flow temperature (see par. 13.2.5 and fig. 21)
0 to 0.9 Volt
= boiler off
1 Volt
= Flow temperature set point 50°F [10°C]
8 Volts
= Flow temperature set point 176°F [80°C]
Output based – fixed parameters (20 to 100%)
Set the value of the boiler control setting parameter to (see fig. 22)
0 to 1.9 Volt
= Boiler off
2 Volt
= Boiler 20% output
10 Volts
= Boiler = 100% output
8.6.4 On/off control (1 X no volt switched pair) internal modulation
The heat output modulates between the minimum and the maximum value based on the set flow temperature,
terminal connections X29-9 and X29-10. Set the value of the boiler control operation parameter to (on/off).
8.6.5 High/low control 2 stage (2 x no volt switched pairs)
The heat output is controlled between part load (50%, adjustable) and full load by means of a two-stage
controller, terminal connection X29-9 and X29-10 low fire; X29-7 and X29-8 high fire.
Set the value of the boiler control operation parameter to . The output percentage on which the
boiler runs on low fire can be adjusted with parameter (low fire start point as percentage) in the setting
mode. The 'high fir e' percentage is dependent of the maximum adjusted output, see setting mode,
parameter (maximum output). During this 'high' state modulation on adjusted flow temperature is
released.
De Dietrich Gas 310/610 ECO
36