Example (Factory setting is always = 0)
▪ Water pressure sensor on = 1
▪ Analog output % = 0
▪ Gas leakage control VPS on = 8
▪ Imperial units of / PSI = 16
The sum of these settings provided parameter setting
(1) + (0) + (8) + (16) =
Table 17 adjustment options/accessories
13.2.14 "low" speed with H/L control ()
Parameter
, adjustable between 10 and 60 (x100) rpm. This setting only applies if the boiler is in High/Low
control mode (parameter
13.2.15 Boiler type ()
This code appears only when replacing the control unit. After placing the new control unit, code appears
automatically in the display. The value must be changed in to the correct value for your boiler type (see
mounting-instructions of the service unit
Boiler water pressure sensor off
Boiler water pressure sensor on
Analog output Heat output %
Analog output Temperature of [°C]
Gas leakage control VPS off
= 21).
57
De Dietrich Gas 310/610 ECO
Options
Gas leakage control VPS on
Metric units °C & bar
Imperial units °F & psi
Parameter :
Value
Sum
0
1
0
4
0
8
0
16
...