12.2 Read-out mode (
Read-out mode is used to display various values. Press the
flashes). Select the required code using the
Code
Description
Flow temperature °F [°C]
Return temperature °F [°C]
Flue gas temperature °F [°C]
Heat exchanger temperature °F [°C]
Flow temperature set point °F [°C]
Heat demand status (1
Air pressure diff. sensor (LDs, 2
Switch-on temperature for central heating
operation °F [°C]
Requested (permitted by boiler control) output
% is displayed, irrespective of boiler control
setting
Calculated output %
Analog input voltage - volts
Control strategy (see section 12.3)
Current water pressure
N/a
Fan speed
Ionization level (flame signal)
Unique boiler code
Pressure difference over air pressure
differential sensor
Table 09 Read-out mode user level
*The displayed value has 4 digits. The display alternately flashes from to with code
indicating the value being read. In this example: fan speed 4000 i.e.
)
key.
Read-out range/comments
Actual value
Actual value
Actual value
Actual value
Calculated value
= on/off contact open
= on/off contact closed
st
digit)
= air pressure diff. sensor °pen
= air pressure diff. sensor closed
nd
digit)
Demanded value
- = 100% demanded value
- = 100% actual value
- = 100% actual value
-
- ÷ 10 bar units, then x 14.5 for
psi units. with pressure sensor (optionally),
no pressure sensor
-
- = x 0.1µA
-
- = x 0.1 mbar, then x 0.4 for
inches w.c. units
49
De Dietrich Gas 310/610 ECO
key until
appears in the code window (dot
Read-out
(e.g.)
then
=
4000*