Efficiency Information; Combustion Efficiency; Thermal Efficiency; Standby Losses - DeDietrich 310 ECO Series Installation And Operating Manual

Gas 310/610 eco series gas-fired condensing hot water boiler
Table of Contents

Advertisement

5 EFFICIENCY INFORMATION

5.1 Combustion efficiency

Theoretically efficiency up to 99.9% can be achieved with return water temperature of 104°F
[40°C], the combustion efficiency according to ANSI Z21.13b-/CSA 4.9b-2007 average = 95.3%
5.2 Thermal efficiency [heat to water]
Average thermal efficiency 97.4%

5.3 Standby losses

Less than 0.3% with an average water temperature of 113°F [45°C]

6 APPLICATION DATA

The Gas 310/610 ECO can be used on all new and retrofit projects in both single and multiple
configurations. Conventional and sealed combustion venting system capability means that the boiler can
be sited almost any-where within a building.
External control systems (BMS) can be interfaced with the boiler to provide on/off – high/low or
modulating (0-10 V dc input) firing control options.
7
INSTALLATION INSTRUCTIONS FOR HEATING INSTALLER

7.1 General

All gas appliances must, by law, be installed by competent person (Licensed gas-heating technician)
It is in your own interest and that of safety to ensure that the law is complied with. The following codes
must be adhered to when the De Dietrich Gas 310/610 ECO is installed:
CSA B149 gas installation code & ANSI Z223.1 / NFPA 54 gas code.
In addition to the above regulations, this boiler must be installed in compliance with:
National & local building codes
ASME CSD-1 as required
CSA & NEC electrical codes
Other Regulations
Important:
The De Dietrich Gas 310/610 ECO is a CSA certified boiler and must not be modified or installed in any
way contrary to these "Installation and maintenance Instructions." Manufacturer's Instructions must NOT
be taken as overriding statutory obligations.

7.2 Delivery and installation

The De Dietrich Gas 310/610 ECO is supplied fully assembled, plastic wrapped and crated on a pallet.
The overall dimensions of the crate are 31.5" [80cm] wide and 68.9" [175 cm] high with the length
dependent on the number of sections (5 & 6 sections: 66.9" [170 cm], 7 to 9 sections: 82.3" [209 cm]).
At the base of the packaging is a 30" [76 cm] wide pallet enabling it to be transported with a pallet truck,
forklift truck or 4-wheel transport boards. Excluding the crate, the boiler is 28.4" [72cm] wide c/w casing
panels and 27 5/8" [70 cm] without casing and will fit through most standard doors (minimum door
opening width 31.5" [80 cm]. The boiler itself has wheels so that, once the packaging has been removed,
it can easily be moved around on a smooth surface. The packaging lid includes a rocking ramp, which
can be used to negotiate obstacles such as doorsteps and small plinths. Once in position the boiler is
fixed into position using the fitted jacking bolts which both raise the wheels of the ground and level the
boiler. Technical documentation is supplied in a holder on the inside of the boiler casing (beneath the
instrument panel). A number of small loose components, such as the 4 support pads and the siphon for
the boiler have been placed in the flue gas discharge.
The Gas 610 ECO boilers consist of a Gas 310-L and a Gas 310-R. Please refer to page 11 for
details.
De Dietrich Gas 310/610 ECO