Sequence Of Operation; Boiler Control; Gas 310 Introduction - DeDietrich 310 ECO Series Installation And Operating Manual

Gas 310/610 eco series gas-fired condensing hot water boiler
Table of Contents

Advertisement

8.5 Switch sequence diagram

8.6 Boiler control

8.6.1 Gas 310 Introduction, Gas 610 each module
The De Dietrich Gas 310/610 ECO can be controlled using one of the following methods:
Note: When using on/off control the boiler will also modulate to maintain the flow temp set point (parameter
Fully modulating, where the output
modulates between the minimum and
maximum value on the basis of the flow
temperature defined by the modulating
controller.
Analog control (0-10 volts), where the
heat output or temperature is controlled
by a 0-10 volt signal.
On/off control, (one-volt free relay) where
the heat output modulates between the
minimum and maximum value on the
basis of the flow temperature set in the
boiler.
High/low control, (two volt free relays) where the
boiler is controlled by means of a 2-stage
controller at part load and full load.
In all cases, modulation is based on the required flow temperature and there is a
the following characteristic. Up to a
output. Between
T full load
of 45°F [25°C] (factory setting, parameter
T
and
the output reduces in linear fashion (see fig. 20).
T part load
De Dietrich Gas 310/610 ECO
34
Fig. 19 Switch sequence diagram [04.31H.79.00003]
Fig. 20 °output control characteristic
dependent output control with
T
) the boiler operates at full
)