Operation Selection On Option Error - Hyundai N300-P Instruction Manual

Economical inverter
Table of Contents

Advertisement

N300-P INSTRUCTION MANUAL
Function to
No.
restrict display
28
b120
29
30
31
C021~
C025,C026
32
33
34
H002
35
H202
36
37
P010
Stabilized factor
When the motor is hunting or unstable, this function can be
adjusted to help stabilize the motor.
When the motor is unstable, check the allowable motor selection (H003/H203) and motor pole selection
(H004/H204) with your motor. If their code data is different from your motor specification, set the right data.
When R1 of usage motor is less then R1 of regular motor, raise the set value of H006/H206 gradually.
When you operate greate motor than rated capacity of inverter, lower the set value of H006/H206.
The following two functions can also assist to reduce hunting or ratting of a motor.
(1) Lower the carrier frequency (b083).
(2) Lower the output voltage gain (A045).
Set item
Output gain
Carrier
frequency
Stabilized factor
H006/H206/H306

Operation selection on option error

When an add-in option is the cause of protective trip this function
can be used to switch the trip facility off and allow the Inverter to
carry on it's operation
Set item
Operation selection
on optional error
Motor constant
Set each constant according to the motor you use.
In case of using several motors in parallel, set the constant values that are closest to the total capacity of the
belonging motor.
Reduced torque or instability may occur while using auto torque boost function if these settings are incorrect.
Code to be restricted display
Data
01
02,06
03
07
21
24,25
26
00
01,02
00
01,02
01
Function code
A045
0.5-12.0 (5.5 to 75kW)
b083
0.5-10.0 (90 to 160kW)
Function code
Data
00
P001/P002
01
Chapter 4 Explanation of function
b121~b126
C042,C043
C040,C041
C055~C058
C063
C045,C046
C111
H020~H024
H030~H034
H220~H224
H230~H234
P011~P023,P025~P027
Data
Units : %
20.-100.
Lower this when hunting occurs
Units : kHz
Lower this when hunting occurs
Raise or lower when hunting occurs.
0.-255.
TRP : inverter trip and output alarm when option error occurs.
Run : inverter ignores this and continues operation
when option error occurs.
Note
Brake control
Frequency arrival signal
Overload advance notice
over torque
Zero speed detection signal
Frequency arrival signal
overload advance notice 2
Motor constant
Motor constant(Auto-tuning)
Motor constant
Motor constant(Auto-tuning)
option function
Relation code
H006/H206/H306 :
st
nd
rd
1 /2 /3 stabilized factor
Description
Relation code
P001:Option1 operation selection on error
P002: Option2 operation selection on error
Description
Relation code
st
nd
H003/H203:1 /2 allowable motor selection
st
nd
H004/H204:1 /2 motor pole selection

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents