N300-P INSTRUCTION MANUAL
(2) Overload advance notice
When the load is high, it is possible to adjust the again by outputting an overload advance notice.
It is used to prevent damage to the machine from too much load, i.e. baggage on a conveyor, the Inverter
overload protection will operate.
Assign 03(OL) or 26(OL2) to an intelligent output terminal 11-15 or the alarm relay output terminal.
(Two kinds of overload advance notice signals are possible output.)
Set item
Overload advance
notice signal output
mode selection
Overload advance
notice Level
Overload restriction
Constant.
Overload restriction level
Overload advance notice level
Function code
Data
C040
0.0
C041
0.1 to
Rated current x 2
0.0
C111
0.1 to
Rated current x 2
(b022/b025)
(C041/C111)
Output current
OL/ OL2
Chapter 4 Explanation of function
On acceleration/deceleration, constant speed,
00
this is valid.
On constant speed only, this is valid.
01
Overload advance notice is non-effective.
Units : A
As load reaches overload advance notice level.
OL signal is output.
Overload advance notice 2 is non-effective.
Units : A
As load reaches overload advance notice level.
OL2 signal is output.
Description