N300-P INSTRUCTION MANUAL
(3) Common specification for 200V/400V class
N300-
Inverter Model
055LFP/HFP
Enclosures
IP20(NEMA1)
Control system
Sine-wave modulation PWM system
Output frequency range
0.1 400Hz
Frequency accuracy
Digital command 0.01% for Max. frequency, analog frequency 0.2% (25 10 )
Frequency resolving power
Digital setting : 0.01Hz, Analog setting : Max. frequency/4000
Voltage/frequency characteristic
V/f option variable, V/f control, (constant torqu e, reduced torque)
Speed fluctuation
0.5%
Overload current rate
120% for 60s,150% for 0.5 second
Stating torque
200% / 0.5Hz
DC Braking
on starting and decelerating by stop command, inverter operates under operation setting
frequency.Or inverter operates with external input (Breaking power, time, frequency can be set.)
Setting by
Operator
DC0 10V, -10 +10V (input impedance 10Kohn), 4 20mA (input impedance 100ohm)
Volume
Extend signal
Setting with RS485 communication
Run/Stop
Operator
Run/
Forward Run/Stop(1a connect),reverse command is impossible on assigning of terminal(selection of 1a, 1b is possible),input of 3 wires is possible.
Volume
Stop
Extend signal
Setting with RS485 communication
Use by selecting terminals from
Intelligent input terminal
Reverse command(RV), multi-speed 1-4(CF1-CF4), jogging(JG), extemal dc braking(DB), 2nd control(SET), 2nd acceleration(2CH), free-run stop(FRS), extemal trip(EXT),
USP function(USP), commercial change(CS), software lock(SFT), analog input voltage/current/select(AT), 3rd control(SET3), reset inverter(RS), 3 wire run(STA), 3wire keep
(STP), 3wire direction selection(F/R), PID selection valid/invalid(PID), PID integrating reset(PIDC), control gain change(CAS), remote control, up function(UP), remote control
down function(DWN), remote control data clear(UDC), compulsion operation(OPE),multi-speed bit 1-7(SF1-SF7), overload ristriction change(OLR), torque limit exist or no(TL),
torque limit change1(TRQ1), torque limit change12(TRQ2), P/PI change(P/PI), brake confirmation (BOK), orientration(ORT),LAD cancel(LAC), position deviation dear(PCLR),
90 degrees the phase difference permission(STAT), permissive input signal for FW/RV(ROK), no assign (NO)
Thermistor input terminal
1 terminal
Signal during rus(RUN), Frequency arrival type 1 signal(FA1), Frequency arrival type 2 signal(FA2), Overload advance notice signal(OL), Output deviation for PID
control(OD), Alarm signal(AL), Arrival signal for only setting frequency(FA3), Over torque(OTQ), Instantaneous stop signal(IP), Under voltage signal(UV), Torque limit
Intelligent output terminal
(TRQ), RUN time over(RNT), ON time over(ONT), Thermal caution(THM), Brake opning(BRK), Brake error(BER), Zero speed detect signal(ZS), Speed deviation
excessive(DSE), Positioning completion(POK), Arrival signal for over setting frequency2(FA4), Arrival signal for only setting frequency2(FA5),
Overload advance notice signal2(OL2), Alarm cord 0-3(AC0-AC3)
Intelligent monitor output terminal
Analog voltage output, analog current output, pulse line output
Output frequency, output current, frequency conversion value, trip history, input output terminal state, input electric power, output voltage, motor torque
Display monitor
V/F free setting(7points), Upper/lower frequency limitter, Frequency jump, curve adjustable speed, manual torque boost level/Braking
point, Analog meter adjustment, Starting frequency, Carrier frequency adjustment, Electronic thermal free setting, External start/end
Other function
(frequency/tate), Analog input selection, Trip retry, Reduced voltage start, Overload restriction, energy-saving operation, Restarting
after an instantaneous power failure, Various kinds signal output, Initialization value setting, Automatic deceleration at the time of
the power supply block, AVR function, Fuzzy, Autotuning(Online/Offline), High torque multi running(Sensor-less vector control with 1
inverters of 2 motors)
0.5 12kHz
Carrier frequency range
Over-current, over-voltage, under-voltage, electronic thermal lecvel, abnormal trouble, ground fault current on starting, instantaneous stop, USP error, open-phase
Protection function
error, control resistoroverload, CT error, external trip, communication error.
Frequency temperature/Preservation
-10
temperature/humidty
5.9m/s (0.6G), 10 55Hz
Vibration
Under 1000m above sea level, indoors (Installed away from corrosive gasses dust)
Using place
Paint color
Grey(Munsell 8.5 YR 6.2 / 0.2 )
Option
Digital input option
4 column BCD, 16bit binary
Operator with copy function, cable for operator, braking resistor, regenerative control unit, altemating reactor, D.C. reactor,
Other options
EMC Mains filter, higher harmonic control unit, LCR filter, applied control installation
200V class
3.5
Schematic mass
(kg)
400V class
3.5
N300-
N300-
N300-
N300-
075LFP/HFP
110LFP/HFP
150LFP/HFP
185LFP/HFP
1 2
key.
50 / -20
65 / 20
90% RH(installed with no dew conensation)
3.5
5
5
12
3.5
5
5
12
Chapter 6 Specification
N300-
N300-
N300-
N300-
220LFP/HFP
300LFP/HFP
370LFP/HFP
450LFP/HFP
2.94m/s (0.3G), 10 55Hz
12
12
20
30
12
12
20
30
N300-
N300-
N300-
N300-
550LFP/HFP
750LFP/HFP
900HFP
1100HFP
180% / 0.5Hz
50
-
-
30
30
30
60
60
N300-
N300-
1320HFP
1600HFP
-
80
80