2.3.2. Setting the Float and Equalize voltages

• Press the
The FLOAT and DC VOLTS indicators light, and the display flashes the
present value of the float voltage. Press and release the
increase or decrease the value in the display by one count, or press and
hold the
or
UP
downward. When the meter displays the desired float voltage, release the
or
key. If you go past the voltage you want, press the
UP
DOWN
key again to reach the voltage you want to set.
• Press the
internally.
The EQLZ and DC VOLTS indicators light, and the display flashes the
present value of the equalize voltage. Press and release the
key to increase or decrease the value in the display by one count, or press
and hold the
downward. When the meter displays the desired equalize voltage, release
the
or
UP
DOWN
key again to reach the voltage you want to set.
DOWN
• Press the
internally.
If you want to adjust the equalize timer duration, skip to Section 2.3.3.
If you want to exit the Edit Mode now, press the
more times until the AT30 returns to normal operation.
If you do not press any front panel key for 25 seconds, Edit Mode ends
automatically, and any change you made to the last setting is not saved.
key.
EDIT/ENTER
key to scroll the value in the display upward or
DOWN
key. The new float voltage setting is saved
EDIT/ENTER
or
key to scroll the value in the display upward or
UP
DOWN
key. If you go past the voltage you want, press the
key. The new equalize voltage setting is saved
EDIT/ENTER