Manual Equalize Method; Auto-Equalize Timer Method - HindlePower AT30 SERIES Operating And Service Instructions

Microprocessor-controlled float battery charger three phase input (25 - 1,000 adc)
Table of Contents

Advertisement

OPERATING THE AT30

Manual Equalize Method

Choose the manual equalize method when you want to equalize charge the
battery, but only when you are able to monitor the battery voltage and
gassing rate. After you select the manual equalize method, press the
key to put the AT30 into the equalize mode. The EQLZ
CHRG MODE
indicator will light.
Press the
CHRG MODE
FLOAT indicator will light.
Never leave the AT30 unattended in the equalize mode
with the manual equalize method selected. A sustained
overcharge may cause permanent damage to the battery.

Auto-Equalize Timer Method

Choose the auto-equalize timer method if you have a flooded (non-sealed)
battery, that is subject to infrequent discharges, or when the battery will be
discharged by at least half of its rated capacity during an ac power failure.
When ac power is restored to the AT30, it turns on in the equalize mode
automatically, and the EQLZ indicator lights. At the end of the equalize
charging time that you select, the AT30 reverts automatically to the float
mode, and the FLOAT indicator lights. At any time during the equalize
charge, you can switch the AT30 back to float mode by pressing the
key. The FLOAT indicator will light.
MODE
Consult your battery manufacturer's instructions before
using the auto-equalize timer method with sealed (valve-
regulated) lead-acid batteries.
Whenever the ac supply fails for 12 seconds or longer, the auto-equalize
timer is enabled. For shorter periods, the timer behaves as listed below:
Mode before
ac failure
FLOAT
EQUALIZE
FLOAT or
EQUALIZE
Switching to Equalize Mode with Auto-Equalize Timer Method Selected
You can start an equalize charge at any time.
• Press the
When the equalize timer is finished, the AT30 reverts automatically to the
float mode, and the FLOAT indicator lights.
28
key again to return the AT30 to the float mode. The
NOTICE
AC falure
duration
less than
12 seconds
less than
12 seconds
12 seconds
or greater
key. The EQLZ indicator will light.
CHRG MODE
CHRG
Mode after
ac failure
FLOAT
Resume EQUALIZE
with time remaining
EQUALIZE
with full time