Using The At30 Front Panel Features; Selecting The Meter Mode - HindlePower AT30 SERIES Operating And Service Instructions

Microprocessor-controlled float battery charger three phase input (25 - 1,000 adc)
Table of Contents

Advertisement

OPERATING THE AT30

2.2. USING THE AT30 FRONT PANEL FEATURES

2.2.1. If the meter displays an error or status message
The AT30 microprocessor control circuitry performs diagnostic checks of
the battery charger during system start-up, then continuously during
operation. If it detects a failure or special status, an intermittent code will
appear on the front instrument panel, displayed between dc output values.
The following table is a list of these error (E ##) and status (A ##) codes.
Code
E 01
E 02
E 03
E 04
E 06
E 07
E 08
E 10
E 12
E 13
E 14
A 01
A 02
A 04
A 05
Pb / nicd
LS-P / LS-S forced load sharing status (primary / secondary)
Codes E 05, E 09, E 11, and A 03 are not used. See Section 3.2 on page
45 for a full explanation of each code.

2.2.2. Selecting the meter mode

• Press the
METER MODE
meter has four operating modes:
1. Alternating between output voltage and output current. When the
AT30 is in a timed equalize mode, the meter alternates between
output voltage, output current, and equalize hours remaining.
2. Displaying output voltage only. The DC Volts indicator lights.
3. Displaying output current only. The DC Amperes indicator lights.
4. Displaying equalize hours remaining only. The EQLZ HRS
REMAINING indicator lights. If the AT30 is not in a timed equalize
mode, the meter displays the full programmed equalize time.
• When the AT30 starts initially, the meter alternates, displaying output
voltage and output current. The DC Volts and DC Amperes indicators
light alternately to indicate what is being displayed.
26
rating resistor R2 open or defective
short circuit on dc output
high dc voltage shutdown occurrence
internal memory failure
voltage sense failure (internal / external / remote)
dc breaker open, or dc output wiring defective
remote TempCo probe defective
open internal feedback loop
internal over-temp circuit defective
rectifier over-temperature occurrence
forced load sharing not working properly
manual equalize enabled for more than 24 hours
equalize mode inhibited
voltmeter calibration inhibited w/TempCo active
dc output at Current Limit setting
battery type for active temperature compensation
key to change the meter display mode. The digital
Explanation