HindlePower AT30 SERIES Operating And Service Instructions page 21

Microprocessor-controlled float battery charger three phase input (25 - 1,000 adc)
Table of Contents

Advertisement

4. Move wire # 38 from TB1(-) to REM SENSE(-).
5. Move wire # 40 from TB1(+) to REM SENSE (+).
6. Connect user-supplied external remote sense leads from the battery or dc bus
to the remote sense terminals on the I/O panel.
7. Replace the two (2) dc output CU-AL compression lugs and tighten all
hardware.
8. Check your work thoroughly. Replace the safety shield (if supplied) before
re-eneregizing the AT30.
9. Restart the AT30 according to the instructions in Section 2.1.
NOTES
1. Use #16 AWG twisted pair.
2. Maximum current is 150 mA.
3. Run leads in their own conduit.
4. Fuse the wiring at the battery or dc bus.
DISABLING REMOTE SENSE
If you ever need to disable remote sense, follow the steps below:
1. De-energize and lock out all ac and dc voltages to the AT30.
2. Check with a voltmeter.
3. Disconnect the remote sense wires from the battery or dc bus first.
4. Remove the remote sense leads from the remote sense (+) and (-) terminals
on the I/O panel (TB1) second.
5. Insulate each lead separately, coil up the wires, and leave them in the bottom
of the AT30, in case you want to wire for remote sense in the future.
6. Reconnect wire # 40 to the dc output (+) terminal.
7. Reconnect wire # 38 to the dc output (-) terminal.
8. Restart the AT30 according to the instructions in Section 2.1.
INSTALLING THE AT30
17