HindlePower AT30 SERIES Operating And Service Instructions page 47

Microprocessor-controlled float battery charger three phase input (25 - 1,000 adc)
Table of Contents

Advertisement

Exercise front
panel controls
Check voltage
and alarm
settings
Final checks
Step
(optional features)
Test auxiliary
alarm relays
Check
integrity of
remote wiring
Final checks
ONLINE SUPPLEMENTS
Preventive Maintenance Procedure
Downloadable Worksheet
Switch from float to equalize, then back
to float.
Turn off the dc circuit breaker. E 07 may
appear on display (requires at least 5% of
rated output current). Reset breaker.
Cycle through meter modes.
Cycle through equalize methods.
Turn off ac circuit breaker. The AC
INPUT FAILURE indicator should light.
Reset breaker.
Use
key to scroll through
EDIT/ENTER
settings. See page 30.
Make sure Plexiglas safety shield is in
place (if supplied).
Restore charger to normal operation.
Close latch on front panel.
Instructions
Press
key and hold for four
LAMP TEST
(4) seconds. Alarm relays will transfer.
Remote sense wiring. See page 16.
Temperature compensation wiring. See
page 20.
Temperature compensation probe. See
page 20.
Close padlock or key lock.
http://www.ATSeries.net/PDFs/JD0064-00.pdf
OPERATING THE AT30
OK
OK
VOLTS
AMPERES
HOURS
MANUAL TIMER
MANUAL EQLZ
AUTO EQLZ TIMER
Alarm OK
FLOAT
EQUALIZE
HVDC
LVDC
Current Limit
OK
OK
OK
Results
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
alarm OK
alarm OK
Adc
43