HindlePower AT30 SERIES Operating And Service Instructions page 55

Microprocessor-controlled float battery charger three phase input (25 - 1,000 adc)
Table of Contents

Advertisement

PROBABLE
SYMPTOM
CAUSE
No output
1. AC supply
current, and
failure
AC ON lamp
2. Input fuse
is out, but ac
F1A/B/C blown
and dc
breakers are
on
3. Defective
wiring
4. Defective
transformer T1
No output
1. Battery is fully
current, but
charged
AC ON lamp
2. Float or
is on, and ac
Equalize voltage
and dc
set too low
breakers are
3. Wrong ac
on
input voltage, or
mis-tapped T1
4. Defective
wiring
5. Defective
rectifier bridge
6. Defective
Gate Driver PC
Board (A15)
7. Defective
transformer T1
8. Defective
inductor L1 or L2
9. Defective dc
breaker (CB2)
RECOMMENDED ACTION
1. If the AC ON indicator is out, check the feeder circuit breaker or
fuse.
2. Remove the ac input fuses (F1A, F1B & F1C) from the fuse
holder(s). Check if blown with an Ohmmeter or fuse tester, and
replace F1A, F1B, and/or F1C as needed.
NOTICE
If replacement fuses immediately blow, see the
Sections titled "AC breaker trips immediately" and "AC breaker
trips after a few minutes" for further troubleshooting hints.
3. Check terminals and wiring between T1 and the rectifier bridge
assembly, main inductor (L1), dc filtering assembly (if present), dc
breaker (CB2), optional dc fuses (F3/F4), and the output terminals
(TB1+/-). Check wires # 42 through # 45 from T1-Y0 through T1-
Y3 to the Gate Driver PC Board connector (J25). Repair as
necessary.
4. Use an ac voltmeter to measure the ac voltage from T1-X1 to
T1-X2 and T1-X3. It is normally 50% to 80% higher than the rated
dc output voltage. If it is too low, check the wiring of the
transformer primary taps (T1-H1 through T1-H3). See Section 1.6
for details. If the ac primary voltage is zero, replace the T1.
1. This is normal operation in a system with little or no dc load. As
long as the AT30 maintains Float voltage, it is operating normally.
2. Check the Float and Equalize voltages and adjust them if
necessary. Consult your battery manufacturer for the proper
voltage settings.
3. Be sure the transformer primary taps (T1-H1, H2 and H3) are
wired correctly for your input voltage. See Section 1.6 for details.
4. Check terminals and wiring between T1 and the rectifier bridge
assembly, main inductor (L1), dc filtering assembly (if present), dc
breaker (CB2), optional dc fuses (F3/F4), and the output terminals
(TB1+/-). Repair as needed.
5. Use an ac voltmeter to measure the voltage between the SCR
gate leads on each SCR module. If you measure about 1.0V rms,
but there is no output current, replace the rectifier module(s)
(A16) as needed.
6. If you do not measure any ac voltage in Step 5 above, and the
battery voltage is less than the Float voltage setting, replace the
Gate Driver PC Board (A15).
7. Use an ac voltmeter to measure the ac voltage between the
transformer secondary taps (T1-X1, T1-X2 & T1-X3). The line-to-
line voltage is normally the same as the rated dc output voltage. If
it is too low, check the wiring of the transformer primary taps (T1-
H1, T1-H2 & T1-H3). See Section 1.6 for details. If the ac voltage
on the transformer secondary taps is zero, replace T1.
8. Disconnect the wiring from inductor (L1) and measure the
resistance between the terminals. If it is an open circuit, replace
L1. Repeat for inductor (L2) if the optional dc filter is installed.
9. Disconnect the battery, and connect a light dc load to the AT30.
Measure the dc voltage across TB1(+) and TB1(-), with the dc
circuit breaker (CB2) on. If no voltage is measured, replace CB2.
SERVICING THE AT30
51