HindlePower AT30 SERIES Operating And Service Instructions page 100

Microprocessor-controlled float battery charger three phase input (25 - 1,000 adc)
Table of Contents

Advertisement

For unpacking and
installation instructions,
see section 1 on page 2 in
this manual
To learn how to use the
equalize timers, see
sections 2.2.4 on page 27
and 2.3.3 on page 32
For details on setting
parameters, see section
2.3 starting on page 30
If you don't press any key
for 25 seconds, the AT30
resumes normal operation
automatically
JA5011-03 - Rev. 05-2012
QUICK OPERATION
Startup
Turn on the dc breaker, labeled "DC OUTPUT".
Turn on the ac breaker, labeled "AC INPUT".
Changing between Float and Equalize Modes
Press the
key to toggle from Float mode to
Equalize mode. Press again to toggle back to Float.
The green or yellow indicator identifies the current mode.
Setting
Float Voltage
Equalize Voltage
Equalize Timer
High DC Voltage
Low DC Voltage
Current Limit
Press the
key. The DC VOLTS and FLOAT
indicators light, and the digital display flashes the present
float voltage setting.
Press the
or
indicates the desired float voltage.
Press the
key to save the new setting internally.
The EDIT sequence advances to the equalize voltage as
shown by the front panel indicators. Repeat the above
steps until you have set all parameters.
Address:
1075 Saint John Street
Easton, PA 18042-6661
Phone:
610.330.9000
Fax:
610.330.8510
Online:
www.hindlepowerinc.com
key until the digital display
©2012 HindlePower, Inc.