Connection Time Before Restore to Ethernet
After using Ethernet (1) and the connection is lost, Ethernet will failover to GPRS. After a specified
time in GPRS mode (2), the unit will attempt to use Ethernet again (3). If the Ethernet connection has
been restored, it will be used again, otherwise GPRS will continue to be used and the cycle will be re-
peated until the Ethernet connection is working again.
1
Ethernet
Access Point Name (APN)
This is the identifying name used to connect to a mobile network. The network operator for the SIM
card can supply this information.
User name / Password
If the connection to the mobile network requires a user name and password, enter these here.
After making these settings, click Save settings.
10.3.5 Proxy Servers
Communication through a proxy server can be set up locally, via the built-in web server in the Netbiter
EasyConnect Gateway.
Ethernet Port to Use
First ensure that the proxy server is set up to use at least one of the following ports:
•
Port 443
•
Port 80
•
Port 5222
If not, the Netbiter EasyConnect Gateway will automatically try to use a port that is open to the Internet.
The ports listed above must be used to communicate with Netbiter Argos. A port on the LAN side
might have another port defined for the proxy, but still needs to use one of the above ports on the WAN
side (port forwarding).
Proxy Types
The type of proxies that can be used are:
•
HTTP
•
Socks 4(a)
•
Socks 5
Obtain access to any credentials required by the proxy server. This information should be provided by
the network administrator.
Netbiter EasyConnect
Doc.Rev. 2.10
2
GPRS
Ethernet
Local Configuration 52
3
Doc.ID. HMSI-168-92
Need help?
Do you have a question about the Netbiter EasyConnect EC150 and is the answer not in the manual?