Outdoor Unit (80 / 90 Class)
1.5

Removal of Fan Motor

Procedure
Step
" Remove the outer panels.
1
Remove the fan motor
lead wire connector
S70.
2
Remove the propeller
fans.
3
Remove 2 screws of
the fan motor mount.
230
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Washer-fitted nut M8
S70
" For reassembling, align
mark of propeller fan with
D-cut section of motor shaft.
" Mount the fan motor so as to
position ! mark on the top.
SiE12-411
Points
Removal Procedure