SiE12-411
D Indoor Heat
1. An indoor heat exchanger thermistor is used for controlling target discharge pipe
Exchanger
Thermistor (DCN)
2. An indoor heat exchanger thermistor is used to prevent freezing.
3. An indoor heat exchanger thermistor is used for anti-icing control.
4. An indoor heat exchanger thermistor is used for detecting incorrect wiring.
Function and Control
temperature.
Set a target discharge pipe temperature according to the outdoor and indoor heat exchanger
temperature.
Control the electronic expansion valve opening so that the target discharge pipe
temperature can be obtained.
During the cooling operation, if the temperature drops abnormally, the operating frequency
becomes lower, then the operation must be halted.
During the cooling operation, if the heat exchanger temperature in the room where operation
is halted becomes -1°C, or if the room temperature - heat exchanger in the room where
operation is halted becomes ≥10°C, it is assumed as icing.
During the operation of checking incorrect wiring, refrigerant is passed in order from the port
A to detect a heat exchanger temperature, and then wiring and piping will be checked.
Function of Main Structural Parts