Removal Of The Fan Motor - Daikin SUPER MULTI NX G Series Service Manual

Table of Contents

Advertisement

SiUS12-928
1.4

Removal of the Fan Motor

Procedure
Step
 Disconnect the connector for
the fan motor and release
the fan motor lead wire.
1
Remove the washer-fitted
nut and remove the
outdoor fan.
2
Remove the 2 screws of
the fan motor mount.
3
Open the 2 clamps and
release the fan motor lead
wire.
Remove the 4 screws to
remove the fan motor.
Removal Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Fan
motor
mount
(Backside)
Outdoor Unit – 2MXS18GVJU
Points
 When reassembling, align
mark of propeller fan with
D-cut section of motor shaft.
 Nut size : M6
Spanner size : 10mm
 When reassembling, fix the
fan motor lead wire to avoid
contact with the outdoor fan.
(R10363)