SiBE05-311 1. Introduction .....................v 1.1 Safety Cautions ..................v Part 1 List of Functions ..............1 1. List of Functions ..................2 1.1 Cooling Only .................... 2 1.2 Heat Pump....................3 Part 2 Specifications..............5 1. Specifications ..................6 1.1 Cooling Only .................... 6 1.2 Heat Pump....................
Page 4
SiBE05-311 3.14 Forced Operation Mode................. 44 3.15 Additional Function ................44 Part 5 System Configuration............45 1. System Configuration................46 2. Instruction....................47 2.1 Safety Precautions ................47 2.2 Names of Parts..................49 2.3 Preparation before Operation ..............52 2.4 AUTO · DRY · COOL · HEAT · FAN Operation ........55 2.5 Adjusting the Air Flow Direction.............
Page 5
SiBE05-311 1.2 Removal of the Front Panel..............117 1.3 Removal of the Horizontal Blade ............119 1.4 Removal of the Signal Receiver Unit / Swing Motor......120 1.5 Removal of the Discharge Grille............121 1.6 Removal of the Drain Pan ..............122 1.7 Removal of the Electrical Box / PCB ...........
SiBE05-311 Introduction 1. Introduction Safety Cautions Cautions and Be sure to read the following safety cautions before conducting repair work. Warnings The caution items are classified into “ Warning” and “ Caution”. The “ Warning” items are especially important since they can lead to death or serious injury if they are not followed closely.
Introduction SiBE05-311 Caution Do not repair the electrical components with wet hands. Working on the equipment with wet hands can cause an electrical shock. Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock. Be sure to provide the grounding when repairing the equipment in a humid or wet place, to avoid electrical shocks.
SiBE05-311 Introduction Warning Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire.
Introduction SiBE05-311 Warning Do not use a joined power cable or extension cable, or share the same power outlet with other electrical appliances, since it can cause an electrical shock, excessive heat generation or fire. Caution Check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure.
SiBE05-311 Part 1 List of Functions 1. List of Functions ..................2 1.1 Cooling Only .................... 2 1.2 Heat Pump....................3 List of Functions...
List of Functions SiBE05-311 1. List of Functions Cooling Only Category Functions Category Functions Inverter (with Inverter Power Control) Air Purifying Filter with Bacteriostatic, –10 Virustatic Functions Operation Limit for Cooling (˚CDB) Basic Function Operation Limit for Heating (˚CWB) — —...
Printed Circuit Board Connector Wiring Diagram SiBE05-311 1. Printed Circuit Board Connector Wiring Diagram Indoor Unit Connectors 1) S6 Connector for swing motor 2) S7 Connector for fan motor 3) S21 Connector for centralized control (HA) 4) S24 Connector for display PCB 5) S25, S27, S36 Connector for control PCB 6) S26 Connector for signal receiver PCB...
Printed Circuit Board Connector Wiring Diagram SiBE05-311 Outdoor Unit Printed circuit board (1) Printed circuit board (2) Name of Connector 1) S10 Connector for PCB (2) 2) S11 Connector for PCB (1) 3) S30 Connector for compressor motor 4) S70 Connector for fan motor 5) S80 Connector for four way valve coil (Heat pump only)
Page 24
SiBE05-311 Printed Circuit Board Connector Wiring Diagram Detail of PCB (1) Connect to S11 on PCB (2) 3P100242-1B Detail of PCB (2) Printed Circuit Board Connector Wiring Diagram...
SiBE05-311 Part 4 Function and Control 1. Main Functions..................18 1.1 Frequency Principle................18 1.2 Auto-Swing .................... 20 1.3 Fan Speed Control for Indoor Units............21 1.4 Programme Dry Function ..............22 1.5 Automatic Operation................23 1.6 Night Set Mode..................24 1.7 Home Leave Operation .................
Main Functions SiBE05-311 1. Main Functions Note: See the list of functions for the functions applicable to different models. Frequency Principle Main Control The compressor is frequency-controlled during normal operation. The target frequency is set by the following 2 parameters coming from the operating indoor unit: Parameters The load condition of the operating indoor unit The difference between the room temperature and the set temperature...
Page 28
SiBE05-311 Main Functions Inverter Features The inverter provides the following features: The regulating capacity can be changed according to the changes in the outdoor air temperature and cooling/heating load. Quick heating and quick cooling The compressor rotational speed is increased when starting the heating (or cooling). This enables a quick set temperature.
Main Functions SiBE05-311 Auto-Swing Auto-Swing The following table explains the auto-swing process for heating, cooling, dry and fan: up and down (automatic) right and left (manual) heating cooling / dry / fan ceiling (R2964) (R2965) (R2963) floor (R2967) (R2966) (R2968) Function and Control...
SiBE05-311 Main Functions Fan Speed Control for Indoor Units Control Mode The airflow rate can be automatically controlled depending on the difference between the set temperature and the room temperature. This is done through phase control and hall IC control. For more information about hall IC, refer to the troubleshooting for fan motor on page 79.
Main Functions SiBE05-311 Programme Dry Function Programme dry function removes humidity while preventing the room temperature from lowering. Since the microcomputer controls both the temperature and air flow volume, the temperature adjustment and fan adjustment buttons are inoperable in this mode. In Case of The microcomputer automatically sets the temperature and fan settings.
SiBE05-311 Main Functions Automatic Operation Automatic Cooling / Heating Function (Heat Pump Only) When the AUTO mode is selected with the remote controller, the microcomputer automatically determines the operation mode from cooling and heating according to the room temperature and setting temperature at the time of the operation startup, and automatically operates in that mode.
Main Functions SiBE05-311 Night Set Mode When the OFF timer is set, the Night Set circuit automatically activates. The Night Set circuit maintains the airflow setting made by users. The Night Set The Night Set circuit continues heating or cooling the room at the set temperature for the first Circuit one hour, then automatically lowers the temperature setting slightly in the case of cooling, or raises it slightly in the case of heating, for economical operations.
SiBE05-311 Main Functions Home Leave Operation Outline In order to respond to the customer's need for immediate heating and cooling of the room after returning home or for house care, a measure to switch the temperature and air volume from that for normal time over to outing time by one touch is provided.
Main Functions SiBE05-311 Inverter Powerful Operation Outline In order to exploit the cooling and heating capacity to full extent, operate the air conditioner by increasing the indoor fan rotating speed and the compressor frequency. Details of the When Powerful button is pushed in each operation mode, the fan speed/setting temperature will Control be converted to the following states in a period of twenty minutes.
SiBE05-311 Main Functions Other Functions 1.9.1 Hot Start Function Heat Pump Only In order to prevent the cold air blast that normally comes when heating is started, the temperature of the heat exchanger of the indoor unit is detected, and either the air flow is stopped or is made very weak thereby carrying out comfortable heating of the room.
Function of Main Structural Parts SiBE05-311 2. Function of Main Structural Parts Main Structural Parts Heat Pump Model Electrontic expansion valve Four way valve Compressor (R2825) Cooling Only Model Electrontic expansion valve Compressor (R2826) Function and Control...
SiBE05-311 Function of Main Structural Parts Function of Thermistor 2.2.1 Heat Pump Model Four way valve Compressor (R2827) A Outdoor Heat 1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature. Exchanger Set a target discharge temperature depending on the outdoor and indoor heat exchanger temperature.
Function of Main Structural Parts SiBE05-311 2.2.2 Cooling Only Model Compressor (R2828) A Outdoor Heat 1. The outdoor heat exchanger thermistor is used for controlling target discharge temperature. Set a target discharge temperature depending on the outdoor and indoor heat exchanger Exchanger temperature.
SiBE05-311 Control Specification 3. Control Specification Mode Hierarchy Outline There are two modes; the mode selected in user’s place (normal air conditioning mode) and forced operation mode for installation and providing service. Detail 1. For heat pump model There are following modes; stop, cooling (includes drying), heating (include defrosting) Air conditioner control mode Forced operating mode Forced cooling (for Pump Down Operation)
Control Specification SiBE05-311 Frequency Control Outline Frequency will be determined according to the difference between room and set temperature. The function is explained as follows. 1. How to determine frequency. 2. Frequency command from an indoor unit. (The difference between a room temperature and the temperature set by the remote controller.) 3.
Page 42
SiBE05-311 Control Specification 3. Determine lower limit frequency Set a maximum value as an lower limit frequency among the frequency lower limits of the following functions: Pressure difference upkeep. 4. Determine prohibited frequency There is a certain prohibited frequency such as a power supply frequency. Indoor Frequency Command (∆D signal) The difference between a room temperature and the temperature set by the remote controller will be taken as the “∆D signal”...
Control Specification SiBE05-311 Controls at Mode Changing / Start-up 3.3.1 Preheating Operation Outline Operate the inverter in the open phase operation with the conditions including the preheating command (only for heat pump model) from the indoor, the outdoor air temperature and discharge pipe temperature.
SiBE05-311 Control Specification Discharge Pipe Control Outline The discharge pipe temperature is used as the compressor's internal temperature. If the discharge pipe temperature rises above a certain level, the operating frequency upper limit is set to keep this temperature from going up further. Detail Divide the Zone Stop zone...
Control Specification SiBE05-311 Freeze-up Protection Control Outline During cooling operation, the signals being sent from the indoor unit allow the operating frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from the indoor unit must be divided into the zones as the followings. Detail Conditions for Start Controlling Judge the controlling start with the indoor heat exchanger temperature after 2 sec from...
SiBE05-311 Control Specification Fan Control Outline Fan control is carried out according to the following priority. 1. Fan ON control for electric component cooling fan 2. Fan control when defrosting 3. Fan OFF delay when stopped 4. ON/OFF control when cooling operation 5.
Control Specification SiBE05-311 3. The set of a constant DOA1CG, DOA2CG, DOA3CG, FCG7 and FCG8 have constants for Cooling / Heating separately and these constants are distinguished with a suffix c/w. Outdoor temperature DOA2CG DOA1CG DOA4CG DOA3CG The lower Cancelled FCG7 FCG8 FCG7...
SiBE05-311 Control Specification 3.11 Defrost Control Outline Heat Pump Only Defrosting is carried out by the cooling cycle (reverse cycle). The defrosting time or outdoor heat exchanger temperature must be more than its fixed value when finishing. Detail Conditions for Starting Defrost The starting conditions must be made with the outdoor air temperature and heat exchanger temperature.
Control Specification SiBE05-311 3.12 Electronic Expansion Valve Control Outline The following items are included in the electronic expansion valve control. Electronic expansion valve is fully closed 1. Electronic expansion valve is fully closed when turning on the power. 2. Pressure equalizing control Open Control 1.
Page 50
SiBE05-311 Control Specification 3.12.1 Fully Closing with Power ON Initialize the electronic expansion valve when turning on the power, set the opening position and develop pressure equalizing. 3.12.2 Pressure Equalization Control When the compressor is stopped, open and close the electronic expansion valve and develop pressure equalization.
Control Specification SiBE05-311 3.12.7 Control when frequency is changed When the target discharge pipe temperature control is active, if the target frequency is changed for a specified value in a certain time period, cancel the target discharge pipe temperature control and change the target opening of the electronic expansion valve according to the shift. 3.12.8 Target Discharge Pipe Temperature Control Obtain the target discharge pipe temperature from the indoor and outdoor heat exchanger temperature, and adjust the electronic expansion valve opening so that the actual discharge...
SiBE05-311 Control Specification 3.13 Malfunctions 3.13.1 Sensor Malfunction Detection Sensor malfunction may occur either in the thermistor or current transformer (CT) system. Relating to Thermistor Malfunction 1. Outdoor heat exchanger thermistor 2. Discharge pipe thermistor 3. Fin thermistor 4. Outdoor air thermistor Relating to CT Malfunction When the output frequency is more than 62 Hz and the input current is less than 0.5A, carry out abnormal adjustment.
Control Specification SiBE05-311 3.14 Forced Operation Mode Outline Forced operating mode includes only forced cooling. Detail Forced Cooling Item Forced Cooling Forced operation 1) The outdoor unit is not abnormal allowing conditions and not in the 3-minute stand-by mode. 2) The operating mode of the outdoor unit is the stop mode.
System Configuration SiBE05-311 1. System Configuration After the installation and test operation of the room air conditioner have been completed, it should be operated and handled as described below. Every user would like to know the correct method of operation of the room air conditioner, to check if it is capable of cooling (or heating) well, and to know a clever method of using it.
Do not attempt to repair, relocate, modify or reinstall the air conditioner by yourself. Incorrect work will cause electric shocks, fire etc. • For repairs and reinstallation, consult your Daikin dealer for advice and information. • The refrigerant used in the air conditioner is safe. Although leaks should not occur,...
Instruction SiBE05-311 • Do not stand or sit on the outdoor unit. Do not place any object on the unit to avoid injury, do not remove the fan guard. • Do not place anything under the indoor or outdoor unit that must be kept away from moisture.
SiBE05-311 Instruction Names of parts Indoor Unit The indoor unit can be installed either to the ceiling or to a wall. The descriptions contained in this manual show the case when installation is being carried out to the ceiling. (The methods of operation used are the same when installing to a wall.) Opening the front grille How to open the front grille: (page 22)
Page 59
Instruction SiBE05-311 Outdoor Unit Indoor Unit 1. Louvres (vertical blades) 13. Indoor unit ON/OFF switch: (page 10.) • The louvres are inside of the air outlet. • Push this switch once to start operation. (page 12.) Push once again to stop it. 2.
Instruction SiBE05-311 Preparation before Operation To set the batteries 1. Press with a finger and slide the front cover to take it off. Position + and 2. Set two dry batteries (AAA). – correctly! 3. Set the front cover as before. ATTENTION About batteries •...
Page 62
SiBE05-311 Instruction To operate the remote controller • To use the remote controller, aim the transmitter at the indoor unit. If there is anything to block signals between the unit and the remote controller, such as a curtain, the unit will not operate. •...
Instruction SiBE05-311 To set the clock 1. Press “CLOCK button”. is displayed. blinks. 2. Press “TIMER setting button” to set the clock to the present time. Holding down “ ” or “ ” button rapidly increases or decreases the time display. 3.
SiBE05-311 Instruction AUTO · DRY · COOL · HEAT · FAN Operation The air conditioner operates with the operation mode of your choice. From the next time on, the air conditioner will operate with the same operation mode. To start operation 1.
Instruction SiBE05-311 To change the air flow rate setting 5. Press “FAN setting button”. DRY mode AUTO or HEAT or COOL or FAN mode “ ” Five levels of air flow rate setting from “ ” plus “ ” “ ”...
SiBE05-311 Instruction Adjusting the Air Flow Direction You can adjust the air flow direction to increase your comfort. To adjust the horizontal blade (flap) 1. Press “SWING button”. The display will light up and the flap will begin to swing. 2.
Page 67
Instruction SiBE05-311 To adjust the vertical blades (louvres) • When adjusting the louvre, use a robust and stable stool and watch your steps carefully. Hold the knob and move the louvres. (You will find a knob on the left side and the right side blades.) Notes on flap and louvres angles •...
SiBE05-311 Instruction POWERFUL Operation POWERFUL operation quickly maximizes the cooling (heating) effect in any operation mode. You can get the maximum capacity. To start POWERFUL operation 1. Press “POWERFUL button”. • POWERFUL operation ends in 20 minutes. Then the system automatically operates again with the settings which were used before POWERFUL operation.
Instruction SiBE05-311 OUTDOOR UNIT SILENT Operation OUTDOOR UNIT SILENT operation lowers the noise level of the outdoor unit by changing the frequency and fan speed on th eoutddor unit. This function is convenient during night. To start OUTDOOR UNIT SILENT operation 1.
SiBE05-311 Instruction HOME LEAVE Operation HOME LEAVE operation is a function which allows you to record your preferred temperature and air flow rate settings. To start HOME LEAVE operation 1. Press “HOME LEAVE button” • The HOME LEAVE lamp lights up. 1, 2 To cancel HOME LEAVE operation HOME LEAVE...
Page 71
Instruction SiBE05-311 What’s the HOME LEAVE operation Is there a set temperature and air flow rate which is most comfortable, a set temperature and air flow rate which you use the most? HOME LEAVE operation is a function that allows you to record your favorite set temperature and air flow rate.
SiBE05-311 Instruction TIMER Operation Timer functions are useful for automatically switching the air conditioner on or off at night or in the morning. You can also use OFF TIMER and ON TIMER in combination. To use OFF TIMER operation • Check that the clock is correct.
Instruction SiBE05-311 To use ON TIMER operation • Check that the clock is correct. If not, set the clock to the present time. (page 9.). 1. Press “ON TIMER button”. is displayed. blinks. 2. Press “TIMER Setting button” until the time setting reaches the point you like.
SiBE05-311 Instruction 2.10 Care and Cleaning CAUTION • Before cleaning, be sure to stop the operation and turn the breaker OFF. UNITS Indoor unit, Outdoor unit and Remote controller 1. Wipe them with dry soft cloth. Front grille 1. Open the front grille. •...
Instruction SiBE05-311 Filters 1. Open the front grille. (page 22) 2. Pull out the air filters. • Push upwards the tab at the center of each air filter, then pull it down. 3. Take off the air purifying filter photocatalytic deodorizing filter. •...
SiBE05-311 Instruction Check Check that the base, stand and other fittings of the outdoor unit are not decayed or corroded. Check that nothing blocks the air inlets and the outlets of the indoor unit and the outdoor unit. Check that the earth wire is not disconnected or broken. Check that the drain comes smoothly out of the drain hose during COOL or DRY operation.
Instruction SiBE05-311 2.11 Troubleshooting These cases are not troubles. The following cases are not air conditioner troubles but have some reasons. You may just continue using it. Case Explanation Operation does not start soon. • This is to protect the air conditioner. •...
SiBE05-311 Instruction Check again. Please check again before calling a repair person. Case Check The air conditioner does not • Hasn’t a breaker turned OFF or a fuse blown? operate. • Isn’t it a power failure? (OPERATION lamp is off) •...
Instruction SiBE05-311 Call the service shop immediately. WARNIING When an abnormality (such as a burning smell) occurs, stop operation and turn the breaker OFF. Continued operation in an abnormal condition may result in troubles, electric shocks or fire. Consult the service shop where you bought the air conditioner. Do not attempt to repair or modify the air conditioner by yourself.
SiBE05-311 Part 6 Service Diagnosis 1. Caution for Diagnosis................72 2. Problem Symptoms and Measures ............73 3. Service Check Function ................74 4. Troubleshooting ..................75 4.1 Error Codes and Description ..............75 4.2 Indoor Unit PCB Abnormality..............76 4.3 Freeze-up Protection Control or High Pressure Control......77 4.4 Fan Motor (AC Motor) or Related Abnormality ........
Caution for Diagnosis SiBE05-311 1. Caution for Diagnosis The Operation lamp flashes when any of the following errors is detected. 1. When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, disabling equipment operation. 2.
SiBE05-311 Problem Symptoms and Measures 2. Problem Symptoms and Measures Symptom Check Item Details of Measure Reference Page None of the units operates. Check the power supply. Check to make sure that the rated voltage is — supplied. Check the type of the indoor units. Check to make sure that the indoor unit type is —...
Service Check Function SiBE05-311 3. Service Check Function In the ARC433A series remote controller, the temperature display sections on the main unit indicate corresponding codes. 1. When the timer cancel button is held down for 5 seconds, a “00” indication flashes on the temperature display section.
SiBE05-311 Troubleshooting 4. Troubleshooting Error Codes and Description Reference Code Indication Description Page System — Normal Insufficient gas Over-voltage detection Signal transmission error (between indoor and outdoor units) Indoor Indoor unit PCB abnormality Unit Freeze-up protection control or high pressure control Fan motor or related abnormality Heat exchanger temperature thermistor abnormality Room temperature thermistor abnormality...
Troubleshooting SiBE05-311 Indoor Unit PCB Abnormality Remote Controller Display Method of Evaluation of zero-cross detection of power supply by indoor unit. Malfunction Detection Malfunction When there is no zero-cross detection in approximately 10 continuous seconds. Decision Conditions Supposed Faulty indoor unit PCB Causes Faulty connector connection Troubleshooting...
SiBE05-311 Troubleshooting Freeze-up Protection Control or High Pressure Control Remote Controller Display Method of High pressure control (heat pump model only) During heating operations, the temperature detected by the indoor heat exchanger Malfunction thermistor is used for the high pressure control (stop, outdoor fan stop, etc.) Detection Freeze-up protection control (operation halt) is activated during cooling operation according to the temperature detected by the indoor unit heat exchanger thermistor.
Page 87
Troubleshooting SiBE05-311 Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. Check No.6 Check the air passage. Refer to P.106 Is there any Provide sufficient air passage. short-circuit? Check the intake air filter. Is it very dirty? Clean the air filter.
SiBE05-311 Troubleshooting Fan Motor (AC Motor) or Related Abnormality Remote Controller Display Method of The rotation speed detected by the hall IC during fan motor operation is used to determine Malfunction abnormal fan motor operation. Detection Malfunction When the detected rotation speed is less than 50% of the HH tap under maximum fan motor Decision rotation demand.
Troubleshooting SiBE05-311 Thermistor or Related Abnormality (Indoor Unit) C4, C9 Remote Controller Display Method of The temperatures detected by the thermistors are used to determine thermistor errors. Malfunction Detection Malfunction When the thermistor input is more than 4.96 V or less than 0.04 V during compressor Decision operation∗.
SiBE05-311 Troubleshooting Signal Transmission Error (between Indoor and Outdoor Units) Remote Controller Display Method of The data received from the outdoor unit in indoor unit-outdoor unit signal transmission is checked whether it is normal. Malfunction Detection Malfunction When the data sent from the outdoor unit cannot be received normally, or when the content of Decision the data is abnormal.
Troubleshooting SiBE05-311 OL Activation (Compressor Overload) Remote Controller Display Method of A compressor overload is detected through compressor OL. Malfunction Detection Malfunction If the compressor OL is activated twice, the system will be shut down. Decision The error counter will reset itself if this or any other error does not occur during the following 60-minute compressor running time (total time).
SiBE05-311 Troubleshooting Compressor Lock Remote Controller Display Method of A compressor lock is detected by checking the compressor running condition through the Malfunction position detection circuit. Detection Malfunction The system judges the compressor lock, and stops due to over current. Decision The system judges the compressor lock, and cannot operation with position detection within 15 seconds after start up.
Troubleshooting SiBE05-311 Input Over Current Detection Remote Controller Display Method of An input over-current is detected by checking the input current value being detected by CT with Malfunction the compressor running. Detection Malfunction The following CT input with the compressor running continues for 2.5 seconds. Decision Cooling: Above 11A, Heating: Above 13A Conditions...
SiBE05-311 Troubleshooting 4.10 Four Way Valve Abnormality Remote Controller Display Method of The indoor air temperature thermistor, the indoor unit heat exchanger thermistor, the outdoor Malfunction temperature thermistor and the outdoor unit heat exchanger thermistor are checked to see if they function within their normal ranges in the operating mode.
Page 95
Troubleshooting SiBE05-311 Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. Check No.5 Refer to P.105 Four way valve coil Correct. disconnected (loose)? Check No.6 Refer to P.106 Harness out of connector? Reconnect.
SiBE05-311 Troubleshooting 4.11 Discharge Pipe Temperature Control Remote Controller Display Method of The discharge pipe temperature control (stop, frequency drooping, etc.) is checked with the Malfunction temperature being detected by the discharge pipe thermistor. Detection Malfunction If a stop takes place 6 times successively due to abnormal discharge pipe temperature, the Decision system will be shut down.
Troubleshooting SiBE05-311 4.12 Position Sensor Abnormality Remote Controller Display Method of FLK(X)S series only Malfunction A compressor startup failure is detected by checking the compressor running condition through the position detection circuit. Detection Malfunction The compressor fails to start in about 15 seconds after the compressor run command signal Decision is sent.
SiBE05-311 Troubleshooting 4.13 CT or Related Abnormality Remote Controller Display Method of A CT or related error is detected by checking the compressor running frequency and CT- Malfunction detected input current. Detection Malfunction The compressor running frequency is below 62 Hz and the CT input is below 0.1 V. Decision (The input current is also below 0.5 A.) If this error repeats 4 times, the system will be shut down.
Page 99
Troubleshooting SiBE05-311 Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. Check No.12 Turn off the power and turn it on again. Refer to P.110 Get the system started. ∗...
SiBE05-311 Troubleshooting 4.14 Thermistor or Related Abnormality (Outdoor Unit) P4, J3, J6, H9 Remote Controller Display Method of This type of error is detected by checking the thermistor input voltage to the microcomputer. Malfunction [A thermistor error is detected by checking the temperature.] Detection Malfunction The thermistor input is above 4.96 V or below 0.04 V with the power on.
Page 101
Troubleshooting SiBE05-311 Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. Check No.6 Turn on the power again. Refer to P.106 Error displayed again Reconnect. on remote controller? Connector or thermistor Reconnect.
SiBE05-311 Troubleshooting 4.15 Electrical Box Temperature Rise Remote Controller Display Method of An electrical box temperature rise is detected by checking the radiation fin thermistor with the Malfunction compressor off. Detection Malfunction With the compressor off, the radiation fin temperature is above 122˚C. (Reset is made when the Decision temperature drops below 113˚C.) Conditions...
Page 103
Troubleshooting SiBE05-311 Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. WARNING Check No.6 Turn off the power and turn it on again. To cool down the electricals, the Refer to P.106 outdoor unit fan gets started when the radiation fin temperature rises...
SiBE05-311 Troubleshooting 4.16 Radiation Fin Temperature Rise Remote Controller Display Method of A radiation fin temperature rise is detected by checking the radiation fin thermistor with the Malfunction compressor on. Detection Malfunction If the radiation fin temperature with the compressor on is above 81˚C, Decision If a radiation fin temperature rise takes place 4 times successively, the system will be shut down.
Page 105
Troubleshooting SiBE05-311 Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. Check No.6 Turn off the power and turn it on Refer to P.106 again to get the system started. Check No.7 Refer to P.107 Error displayed again?
SiBE05-311 Troubleshooting 4.17 Output Over Current Detection Remote Controller Display Method of An output over-current is detected by checking the current that flows in the inverter DC section. Malfunction Detection Malfunction A position signal error occurs while the compressor is running. Decision A speed error occurs while the compressor is running.
Page 107
Troubleshooting SiBE05-311 Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. ∗ An output over-current may result from wrong internal wiring. If the wires have been disconnected and Check No.7 reconnected for part replacement, for example, and the system is interrupted by an output over-current, Refer to P.107 take the following procedure.
SiBE05-311 Troubleshooting 4.18 Insufficient Gas Remote Controller Display Method of Gas shortage detection I : A gas shortage is detected by checking the CT-detected input current Malfunction value and the compressor running frequency. Gas shortage detection II : A gas shortage is detected by checking the difference between Detection indoor unit heat exchanger temperature and room temperature as well as the difference between outdoor unit heat exchanger temperature and room temperature.
Page 109
Troubleshooting SiBE05-311 Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. Check No.4 Refer to P.104 Any thermistor Reconnect in position. disconnected? * Discharge pipe thermistor * Indoor / outdoor unit heat exchanger thermistor Check No.6 * Room temperature thermistor Refer to P.106...
SiBE05-311 Troubleshooting 4.19 Over-voltage Detection Remote Controller Display Method of An abnormal voltage rise is detected by checking the specified over-voltage detection circuit. Malfunction Detection Malfunction An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer Decision (The voltage is over 400V).
Troubleshooting SiBE05-311 4.20 High Pressure Control in Cooling Remote Controller Display Method of High-pressure control (stop, frequency drop, etc.) is activated in the cooling mode if the Malfunction temperature being sensed by the heat exchanger thermistor exceeds the limit. Detection Malfunction Activated when the temperature being sensed by the heat exchanger thermistor rises above Decision...
Page 112
SiBE05-311 Troubleshooting Troubleshooting Be sure to turn off power switch before connect or disconnect connector, Caution or parts damage may be occurred. Check No.4 Check the installation space. Refer to P.104 Check No.7 Abnormal Check No.6 Installation condition Change the air outlet grille check position.
Check SiBE05-311 5. Check How to Check 5.1.1 Electronic Expansion Valve Check Check No.4 Conduct the followings to check the electronic expansion valve (EV). 1. Check to see if the EV connector is correctly inserted in the PCB. Compare the EV unit and the connector number.
SiBE05-311 Check 5.1.2 Four Way Valve Performance Check Check No.5 Turn off the power and turn it on again. ∗ Four way valve coil Cooling / dry : No continuity Start the heating-mode run. Heating : Continuity S80 voltage at DC 180-220 V with Replace the outdoor unit compressor on? PCB.
Check SiBE05-311 5.1.3 Thermistor Resistance Check Check No.6 Remove the connectors of the thermistors on the PCB, and measure the resistance of each thermistor using tester. The relationship between normal temperature and resistance is shown in the graph and the table below.
SiBE05-311 Check 5.1.4 Installation Condition Check Check No.7 Installation condition check Check the allowable Abnormal Change the position of the air dimensions of the air suction discharge grille or the and discharge area. installation location. Normal Does the discharged air from other outdoor Change the position of the air unit cause an increase of discharge grille or the...
Check SiBE05-311 5.1.5 Discharge Pressure Check Check No.8 Discharge pressure check High Replace compessor. Open the stop valve. Is the stop valve open? Is the Replace the pipe installed at connection pipe deformed? the site. Dirty Are the heat exchanger and Clean.
SiBE05-311 Check 5.1.7 Power Supply Waveforms Check Check No.10 Measure the power supply waveform between pins 1 and 3 on the terminal board, and check the waveform disturbance. Check to see if the power supply waveform is a sine wave (Fig.1). Check to see if there is waveform disturbance near the zero cross (sections circled in Fig.2) [Fig.1] [Fig.2]...
Check SiBE05-311 5.1.9 Capacitor Voltage Check Check No.12 < Measuring method > Before measuring, operate the unit for several minutes, then shut down the operation by force using the circuit breaker. If the unit is shut down using the remote controller instead of the circuit breaker, the capacitor discharges the electric load, thus disallowing accurate measurement.
SiBE05-311 Check <Measuring positions> MULTIMETER (DC, VOLTAGA RANGE) TRM1 S90 THERMISTOR LEAD WIRE S80 FOUR WAY VALVE LEAD WIRE (Heating Pump only) S70 FAN MOTOR LEAD WIRE REACTOR LEAD WIRE COMPRESSOR LEAD WIRE (R2956) 5.1.11 Hall IC Check Check No.16 1.
SiBE05-311 Part 7 Removal Procedure 1. Indoor Unit...................114 1.1 Removal of the Air Filter / Front Grille ..........114 1.2 Removal of the Front Panel..............117 1.3 Removal of the Horizontal Blade ............119 1.4 Removal of the Signal Receiver Unit / Swing Motor......120 1.5 Removal of the Discharge Grille............
Indoor Unit SiBE05-311 1. Indoor Unit Removal of the Air Filter / Front Grille Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Features Ceiling-suspended type and floor- mounted type are provided.
Page 124
SiBE05-311 Indoor Unit Step Procedure Points Holding the tab at the center of filter frame, pull the air filter forward. Air filter (R2980) Remove the air filter by Installing filters can be done pulling along the slide easily by sliding-in along the guide.
Page 125
Indoor Unit SiBE05-311 Step Procedure Points To remove the front grille, disengage hooks at three locations. 4. Remove the side panel cover. Side panel cover Remove the side panel cover for removing of suspension parts. Note: If it is difficult to remove side panel from outside with finger, remove front panel first, then...
SiBE05-311 Indoor Unit Removal of the Front Panel Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the four screws located at the back of the front panel. Front panel (R2986) Note:...
Page 127
Indoor Unit SiBE05-311 Step Procedure Points Disengage the three hooks of the front panel Hook located at discharge port. (R2989) Press A-section slightly at the center of the front panel, and disengage hook. Remove the front panel. Caution For ceiling-suspended type, be careful that the front panel may fall when hooks are disengaged.
SiBE05-311 Indoor Unit Removal of the Horizontal Blade Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Open the horizontal blade. Horizontal blade (R2992) Deflect the three center bearings to left side slightly, and disengage shaft of blade.
Indoor Unit SiBE05-311 Removal of the Signal Receiver Unit / Swing Motor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the signal receiver unit. Disengage the two hooks (left and right sides) to remove the...
SiBE05-311 Indoor Unit Removal of the Discharge Grille Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the two screws securing discharge grille. Discharge grille (R2999) Disengage the two hooks (left and right sides) and remove the...
Indoor Unit SiBE05-311 Removal of the Drain Pan Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Disconnect the drain Caution hose. Be careful not to wet the floor with drain water.
SiBE05-311 Indoor Unit Removal of the Electrical Box / PCB Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the PCB. Disconnect the earth wire and the indoor heat exchanger thermistor harness.
Page 133
Indoor Unit SiBE05-311 Step Procedure Points Power supply PCB. Control PCB. (R3009) The illustration shows the control PCB (indoor unit). (R2958) Disconnect the terminals from the terminal strip board. Terminal strip board GRN/YLW Power supply PCB. (R3011) Removal Procedure...
Page 134
SiBE05-311 Indoor Unit Step Procedure Points The illustration shows the power supply PCB (indoor unit). (R2959) 2. Remove the electrical box. Slide the box to direction first to disengage Remove the two hooks. screws. Remove the electrical box by sliding it to disengage the hooks located at the opposite side of the...
Indoor Unit SiBE05-311 Removal of the Fan Rotor / Fan Motor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the three fan rotor covers. (Securing hooks are located at A and B-section.) A-section...
Page 136
SiBE05-311 Indoor Unit Step Procedure Points Remove the two screws to remove fan motor fixtures. Remove the bearing fixture. Bearing Fan motor fixture Bearing fixture (R3018) Loosen the shaft supporting section using a hexagonal wrench (for M6) to remove the fan motor. Removal Procedure...
Indoor Unit SiBE05-311 Removal of the Heat Exchanger Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Be sure to conduct pump Heat exchanger side down operation before disassembling refrigerant Auxiliary flexible tube pipe.
Page 138
SiBE05-311 Indoor Unit Step Procedure Points Hooking piece is Warning! located on the piping Do not contaminate any gas side of the heat exchanger. (including air) other than the specified refrigerant (R410A) into refrigerating cycle. (Contaminating of air or other gas causes abnormal temperature rise in refrigerating cycle, and this...
Outdoor Unit SiBE05-311 2. Outdoor Unit Removal of External Casing Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points The stop valve cover can be removed when the fixed screw is Stop valve cover...
Page 140
SiBE05-311 Outdoor Unit Step Procedure Points The top plate and the Top plate front plate are constructed in a monoblock. Remove the three screws on the right side and the two screws on the front plate. Front plate (R1452) Remove the three screws on the left side.
Page 141
Outdoor Unit SiBE05-311 Step Procedure Points The front plate and the Sectional view at the front. left side plate can be Top plate removed when the one fixed screw is removed. The edge of the top plate gets into this groove. Left side plate (R1737)
SiBE05-311 Outdoor Unit Removal of Bell mouth and Left Side Plate Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points The bell mouth is Remove the bell mouth from attached to the front the front plate after removing Hook A...
Outdoor Unit SiBE05-311 Removal of PCB and Electrical Box Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the shelter. The shelter has five hooks. Be sure to avoid forgetting to Undo the five hooks restore the shelter and to...
Page 144
SiBE05-311 Outdoor Unit Step Procedure Points Remove the four screws fixing the PCB. Disconnect the wire harness. Disconnect the two connectors of the reactor. Removal Procedure...
Page 145
Outdoor Unit SiBE05-311 Step Procedure Points Undo the eight hooks The PCB has eight hooks. and the PCB can be disengaged. Disconnect the three wires from the PCB. Removal Procedure...
Page 146
SiBE05-311 Outdoor Unit Step Procedure Points The PCB can completely be released. 3. Remove the electrical box. Remove the two screws Electrical box fixing the electrical box. (R3053) Removal Procedure...
Page 147
Outdoor Unit SiBE05-311 Step Procedure Points Lift and remove the electrical box. 4. Remove the molded interconnect device (MID). Remove the one screw fixing the MID. Removal Procedure...
Page 148
SiBE05-311 Outdoor Unit Step Procedure Points Slide the MID upward and release. Removal Procedure...
Outdoor Unit SiBE05-311 Removal of Propeller Fan and Fan Motor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Disconnect the fan motor Remove the external plates connector S70.
Page 150
SiBE05-311 Outdoor Unit Step Procedure Points Remove the fan motor. Removal Procedure...
Outdoor Unit SiBE05-311 Removal of Compressor Noise Absorption Pad Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the right side plate. Remove the three screws for removing the right side plate.
Page 152
SiBE05-311 Outdoor Unit Step Procedure Points Pull out the noise absorption pad for the body. Noise absorption pad for the body (R1482) Pull out the top pad of Since the slit prepared for the noise absorption the piping on the noise (a).
Outdoor Unit SiBE05-311 Removal of Partition Plate and Reactor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the partition plate. Remove the two screws fixing the partition plate.
Page 154
SiBE05-311 Outdoor Unit Step Procedure Points When restoring the partition plate, fit the hook into the bottom frame. Hook (R1487) 2. Remove the reactor. The reactor can be released by removing the fixed screw. 3. Remove the reactor assembly. Remove the one screw fixing the reactor assembly to the bottom frame.
Page 155
Outdoor Unit SiBE05-311 Step Procedure Points Slide the reactor assembly this side and release. Removal Procedure...
SiBE05-311 Outdoor Unit Removal of Four Way Valve and Motor Valve Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work Step Procedure Points 1. Remove the parts around the four way valve. Remove the terminal cover and the lead wires of the...
Page 157
Outdoor Unit SiBE05-311 Step Procedure Points Remove the motor valve coil. Motor valve coil (R1494) Confirm that the refrigerant is completely Caution empty in the refrigerant Be careful about four-way circuit before starting valve, pipes and so on, which work. were heated up by a gas Four-way valve...
Page 158
SiBE05-311 Outdoor Unit Step Procedure Points Heat up the brazing parts and withdraw the pipes connected to the In case that the removal seems four way valve by pliers to be hard; and so on. 1. Remove the piping connection part (brazing part) which is easy to remove and restore.
Outdoor Unit SiBE05-311 Removal of Compressor Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the parts around Be careful so as not to burn the compressor.
Page 160
SiBE05-311 Outdoor Unit Step Procedure Points The mounting nut for Remove the four way valve the compressor is only and the motor valve also so Motor valve one piece. as not to be burnt out. coil Remove the nut by an open-end wrench.
Page 161
Outdoor Unit SiBE05-311 Step Procedure Points Confirm that the refrigerant is completely empty in the refrigerant Warning! circuit before starting Since it may happen that work. refrigeration oil in the compressor will catch fire, Be sure to apply prepare wet cloth so as to nitrogen’s replacement extinguish the fire quickly.
SiBE05-311 Part 8 Others 1. Others ....................154 1.1 Test Run from the Remote Controller..........154 1.2 Jumper Settings................... 155 Others...
Others SiBE05-311 1. Others Test Run from the Remote Controller For Heat pump In cooling mode, select the lowest programmable temperature; in heating mode, select the highest programmable temperature. Trial operation may be disabled in either mode depending on the room temperature. After trial operation is complete, set the temperature to a normal level.
SiBE05-311 Others Jumper Settings 1.2.1 When Two Units are Installed in One Room When two indoor units are installed in one room, the two wireless remote controllers can be set for different addresses. How to set the different addresses Control PCB of the indoor unit (1) Remove the front grille.
Piping Diagrams SiBE05-311 1. Piping Diagrams Indoor Units FLKS25BVMB, FLKS35BVMB, FLK25BVMB, FLK35BVMB FLXS25BVMB, FLXS35BVMB, FLX25BVMB, FLX35BVMB INDOOR UNIT CuT ) HEAT EXCHANGER THERMISTOR ON HEAT EXCH. FIELD PIPING SIROCCO FAN ( 6.4CuT ) FAN MOTOR FLX25,35- FIELD PIPING CuT )
SiBE05-311 Wiring Diagrams 2. Wiring Diagrams Indoor Units FLKS25BVMB, FLKS35BVMB, FLK25BVMB, FLK35BVMB FLXS25BVMB, FLXS35BVMB, FLX25BVMB, FLX35BVMB PCB3 PCB1 PCB2 3.15A → outdoor FIELD WIRING. / YLW PCB4 TRANSMISSION CIRCUIT CAUTION NOTE THAT OPERATION WILL SIGNAL RESTART AUTOMATICALLY IF RECEIVER THE MAIN POWER SUPPLY IS...
Page 180
Daikin Europe N.V. is approved by LRQA for its Quality Daikin units comply with the European regulations that Management System in accordance with the ISO9001 guarantee the safety of the product. standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.