Hour Zones In Area 1; Chime Zones In Area 1; Chime 2 Zones In Area 1; Hour Zone In Area - Gemini GEM-P9600 Programming Instructions Manual

Control panel/communicator
Hide thumbs Also See for GEM-P9600:
Table of Contents

Advertisement

WI 1185 6/03
24 Hour Zones in Area 1 (New Program Only)
Ent24H
Zn#XX
NOTE: 24 Hour Zones will automatically be programmed as audible (Burg Output).
(Direct Entry)
Chime Zones in Area 1 (New Program Only)
EntCZ1
Zn#XX
NOTE: A chime time of 2 seconds will be automatically programmed.
(Direct Entry)

Chime 2 Zones in Area 1

EntCZ2
Zn#XX
NOTE: A chime time of 2 seconds will be automatically programmed.
(Direct Entry)
EntEE2

Exit/Entry2 Zones in Area 1

Zn#XX
(Direct Entry)
NOTE: An Exit/Entry 2 Entry Time of 30 seconds will automatically be programmed.
50 mS Loop Response Zones
Ent50m
Zn#XX
zones 01-08 can be programmed for Quick Loop Response. All other zones can be programmed via their respective EZM's
(Direct Entry)
(hardwire).

Aux Output Activated on Alarm Zones

EntAux
Zn#XX
NOTE: An Aux Output Timeout of 15 minutes will automatically be programmed.
(Direct Entry)

Sensor Watch Zones

Ent SW
Zn#XX
NOTE: A Sensor Watch Time of 24 hours will automatically be programmed.
(Direct Entry)

Keypad Sounder On Alarm Zones

EntKPS
Zn#XX
(Direct Entry)

Auto Bypass Re-entry Zones

EntAUB
Zn#XX
(Direct Entry)
when the zone is subsequently closed.
L
NAPCO Security Systems
Enter the zone numbers of zones to be used as 24 Hour zones.
Valid entries are from 01 to 96. Directly enter each zone number, including leading zeros.
U
Press
to save and repeat for any additional zone(s); press the NEXT/YES button to proceed.
Enter the zone numbers which are to be used as Chime Zones.
Valid entries are from 01 to 96. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s), press the NEXT/YES button to proceed.
(New Program Only)
Enter the zone numbers which are to be used as Chime 2 Zones.
Valid entries are from 01 to 96. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s), press the NEXT/YES button to proceed.
Chime 2 zones give a distinct pulsating tone when zone is faulted.
(New Program Only)
Enter the zone numbers of zones to be used as Exit/Entry zones.
Valid entries are from 01 to 96. Directly enter each zone number, including leading zeros.
U
Press
to save and repeat for any additional zone(s), press the NEXT/YES button to proceed.
(New Program Only)
Enter the zone numbers of zones to have a 50mS loop response.
Valid entries are from 01 to 08. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s), press the NEXT/YES button to proceed. Note: Only panel
Note: 750mS is required for Loop Response time in UL installations.
Enter the zone numbers of zones to activate the Aux Output upon alarm.
Valid entries are from 01 to 96. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s); press the NEXT/YES button to proceed.
(New Program Only)
Enter the zone numbers of zones to be Sensor Watch zones.
Valid entries are from 01 to 96. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s), press the NEXT/YES button to proceed.
Enter the zone numbers of all zones to activate the Keypad Sounder upon alarm.
Valid entries are from 01 to 96. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s), press the NEXT/YES button to proceed.
(New Program Only)
Enter the zone numbers of zones to be Auto Bypass Re-entry zones.
Valid entries are from 01 to 96. Directly enter each zone number, including leading zeros.
U
Press
to save and then repeat for any additional zone(s), press the NEXT/YES button to proceed.
Auto Bypass Re-entry Zones allow the system to be armed with the zone faulted but come back into the system (armed)
(New Program Only)
(New Program Only)
(Not evaluated by UL)
X
GEM-P9600 Programming Instructions
!
Page 7