Program Menu - Elgar SW 5550AE Operation Manual

Smartwave switching amplifier
Table of Contents

Advertisement

SW 5550AE • SW 3700AE • SW 1850AE
3.3.2

PROGRAM Menu

The PROGRAM menu allows you to:
Select a phase
Program amplitude–function polarity validates the amplitude input,
see Section 3.4 for more information
Program current limit, either value or level
Program frequency–maximum frequency is determined by the selected
waveforms for each phase, see Section 3.4, Front Panel Programming
Conventions, for more information about maximum frequency
Program phase offset (phase offset represents a phase lead)
Select a function to be output on the selected phase.
MAIN MENU
PROGRAM
MEASURE
WAVEFORM
SEQUENCE
INSTR
SYSTEM
PROGRAM Menu Status and Information Data:
Menu Item
Status and Information Line
PHASE A
[<enter> for next phase]
AMPL
[program output RMS/DC voltage] *
CURL
[program RMS/DC current limit]
FREQ
[program output frequency]
(default: 60 Hz)
θ ANG
[program phase angle offset]
FUNC
[program output waveform]
Operation Manual
OUTPUT [OFF]
PHASE A (or B or C)
AMPL
CURL
FREQ
θ
ANG
FUNC
Range/Default
Phases A, B, C
0–156 V or 0–312 V
(to 0.01V resolution)
0–16 A or 0–8 A (default: 5A)
*
40–63 Hz or 40–500 Hz
0–360° (default: 0°, 120°, 240°)
**
Default: Sine
Operation
V
A
Hz
Deg
3-5