2.5.8
AC Wiring Confi guration (ME2000 models)
The following table provides the different wiring confi gurations for installing and connecting the
AC conductors into and out of ME2000 model inverters (see Figures 2-16 and 2-17 for installation
diagrams showing these confi gurations).
Table 2-4, AC Input/Output Wiring Confi gurations (ME2000 models)
© 2010 Magnum Energy, Inc.
SI/SO (30A)
Single In/
Single Out
(30A)
AC Source
120 VAC @
1
Required
< 30 amps
Reason to
Have an 120
Use
VAC source
that is < 30
amps.
Requires
a separate
inverter
sub-panel.
Appropriate
ME2000
Models
Maximum
30A
Input
(single pole)
Breaker
-
Required
#10 AWG
-
(In & Out)
Minimum
Wire Size
Maximum
3600W
Inverter
(30A @
Pass-thru
120 VAC)
capacity
Wiring
Figure 2-16
Diagram
Note 1: AC Source is from either shore power or an
onboard generator.
SI/DO
Single In/
Dual Out
120 VAC @
< 30 amps
@ < 15 amps per
leg (-15B models);
or < 20 amps per
leg (-20B models).
Do not want to
install a separate
inverter sub-panel.
Inverter pass-thru
capability limited
by model used.
ME2000-15B
ME2000-20B
-15B models:
30A (single pole);
-20B models:
30A (single pole)
-
#10 AWG (In)
(Hot input must
be split to two
#12 AWG);
#12 AWG x2 (Out)
-15B models:
15A/leg
(30A max.);
-20B models:
20A/leg
(30A max.)
Figure 2-17
Installation