Installation
2.5.3
Recommended GFCI (Ground Fault Circuit Interruption) Breakers
Some electrical safety codes require the use of GFCI's. In compliance with UL standards, Magnum
Energy has tested the following GFCI's and fi nd that they function properly when connected to
the inverter's AC output:
2.5.4
AC Terminal Block Connections (ME2012, ME2512, and ME3112 models)
The inverter for these models has a six-pole AC terminal block and one AC ground terminal to
connect the inverter's AC input and output wiring. To access and view the AC terminal block and
ground terminal, remove the two Phillips screws holding the AC Access Cover plate (see Figure 1-3,
Item 15).
Each connection on the AC terminal block is rated to accept one #14 to #6 AWG (2.1 to 13.3 mm
CU stranded wire, or two #12 AWG (3.3 mm
head screw, and the maximum tightening torque is 16 in lbf (1.8 N-m).
Info: One of the AC wiring confi gurations [SI/SO (60A), Figure 2-12] uses a #6 AWG
(13.3 mm
) CU wire to carry 60 amps, and splits to two wires to allow 30 amps for
2
each leg (i.e., AC HOT1 and AC HOT2). IDEAL Industries Inc. (www.idealindustries.
com) manufactures a crimp connector (PN: 412) and a separate insulator (PN: 417)
that allow up to two #8 AWG (8.4 mm
connected together.
Info: For marine installations and to comply with standard safety requirements, the
six-pole AC terminal is provided with a stainless steel wire protector to prevent wire
damage from the set-screw.
Info: The inverter's NEUT IN and NEUT OUT terminals are electrically isolated from
each other while inverting. This is related to the neutral-ground bonding requirement
and helps to prevent ground-loops (see Section 2.6.3 for more information).
The AC ground terminal can accept one #14 to #6 AWG (2.1 to 13 mm
a slotted head screw and has a recommended maximum tightening torque of 45 in lbf (5.1 N-m).
For multiple ground wires, use a pressure or mechanical connector to attach the single wire from
the AC ground terminal to the input and output ground connections.
HOT 1 OUT
HOT 2 OUT
NEUT OUT
Page 21
Shock Sentry
#XGF15V-SP
TM
Leviton Smart Lock #8899-A
Hubbel #GF520EMBKA
) CU stranded wires. The connection uses a M3.5 slotted
2
) wires, with one #6 AWG (13 mm
2

Figure 2-10, AC Terminal Block

) wire to be
2
) CU stranded wire. It uses
2
HOT 2 IN
HOT 1 IN
NEUT IN
AC GROUND
(In & Out)