Factory Default Values; Table 3-2, Inverter/Charger Default Values - Magnum Energy ME Series Owner's Manual

Me series modifi ed sine wave inverter/chargers
Hide thumbs Also See for ME Series:
Table of Contents

Advertisement

Operation
3.8

Factory Default Values

Your ME Series inverter/charger uses default values for the adjustable settings (see Table 3-2) that
are adequate for most installations. If some of your operating parameters need to be changed from
the default values, the optional ME-RC50 remote control can be used to make those changes. To
help you determine if you need the ME-RC50 remote display, information on the inverter/charger
settings that can be changed is provided below. The settings, once programmed, are saved in the
remote's non-volatile memory and are preserved until changed – even if DC power to the inverter
is lost (as long as the ME-RC50 remote is connected). For information on the full range of settings
for each function, refer to the ME-RC50 Owner's Manual at www.magnumenergy.com.
Shore: This setting ensures the inverter AC loads receive the maximum current available
from the shore power or generator. When the total current used to power the AC loads and
to charge the batteries begins to approach the Shore setting, the current that was used
for charging the batteries will automatically be reduced.
01 Search Watts: This setting allows you to turn off the power-saving Search Mode circuitry
or adjust the power level at which the inverter will "wake up" and start inverting.
02 LowBattCutOut: This setting determines when the inverter will turn off based on
low battery voltage. The inverter turns off automatically after the battery voltage has
been below this setting for more than one minute. This protects the batteries from over-
discharge and the AC loads from unregulated power (brown-outs).
03 Batt AmpHrs: This setting allows the user to input the battery bank size in amp hours,
which tells the charger how long to charge the batteries in the Absorb Charge stage.
04 Battery Type: Sets the type of batteries being used in the system; this information
tells the charger what voltage level to use to charge the batteries.
05 Charge Rate: This setting can be used to turn off the charger, limit the amount of
current that the charger can use (leaving more current available to power loads); or, to
ensure small battery banks are not overheated because of a too high charge rate.
06 VAC Dropout: Sets the minimum AC voltage that must be present on the AC input
before the unit transfers from Standby Mode to Inverter Mode. This protects the AC loads
from shore power outages and brown-outs.
Using the ME-RC50 remote also provides the following features:
allows you to enable an equalize charge for certain battery types
displays inverter/charger's operating status
provides fault information for troubleshooting
Adjustable Settings
Shore
01 Search Watts
02 LowBattCutOut
03 Batt AmpHrs
04 Battery Type
05 Charge Rate
06 VAC Dropout
Page 45

Table 3-2, Inverter/Charger Default Values

Default Values
30 amps
5 watts
10 VDC (12-volt models)
600 Amp Hours (Absorb Time = 120 minutes)
Flooded - Liquid Lead Acid
100%
80 VAC
© 2010 Magnum Energy, Inc

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Me2000-20bMe2000-15bMe2012-20bMe2012-15bMe2512Me3112

Table of Contents