Harvest Cycle Circuitry - Manitowoc SD0302A Technician's Handbook

S series; s300 series; s420 series; s450 series; s500 series; s850 series; s1000 series; s1200 series; s1400w series; s1400a series; s1400n series; s1800w series; s1800a series; s1800n series
Hide thumbs Also See for SD0302A:
Table of Contents

Advertisement

HARVEST CYCLE CIRCUITRY

The water level probe does not control the water inlet
valve during the harvest cycle. During the harvest
cycle water purge, the water inlet valve energizes and
de-energizes strictly by time. The harvest water purge
may be set at 45 seconds (top and center terminals) or
0 seconds (center and bottom terminals). Set the
harvest water purge to 0 seconds when reverse
osmosis or deionized water is used. Use the factory
setting of 45 seconds for all other types of water.
45 Second
Jumper
Position
0 Second
Jumper
Position
150
Part Number 80-1479-3 7/10