Table 2–7 Input Currents for 3-Phase Input Power
REQ'D INPUT
TERMINAL
JUMPER
CONNECTIONS
SW 5250A
PFC* USA
F1 to F2
F1 to F2,
PFC INTL
F2 to F3
SW 3500A
PFC USA
F1 & F2
F1 to F2,
PFC INTL
F2 to F3
SW 1750A
PFC USA
None
PFC INTL
None
* Only Phase A and Phase B are present at the output.
Operation Manual
MAXIMUM
MAXIMUM
LINE
NEUTRAL
CURRENT
CURRENT
25A RMS
Not Required
13A RMS
13A RMS
39A RMS
Not Required
39A RMS
68A RMS
25A RMS
Not Required
13A RMS
13A RMS
26A RMS
Not Required
26A RMS
45A RMS
14A RMS
Not Required
13A RMS
13A RMS
13A RMS
Not Required
13A RMS
23A RMS
CONNECT 1-
PHASE INPUT
POWER TO
F1, F3
F1, Neutral
VRMS, L-N
F1, F3
F1, Neutral
F1, F3
F1, Neutral
Table 2–8 Single-Phase Input Configurations
F1-F3
FUSE
RATING
40A
20A
50A
50A
40A
20A
40A
40A
20A
20A
20A
20A
MAXIMUM
VOLTAGE
INPUT
CURRENT
187-264
28A RMS
VRMS, L-L
187-264
42A RMS
187-264
28A RMS
VRMS L-L
187-264
28A RMS
VRMS L-N
187-264
14A RMS
VRMS L-L
187-264
14A RMS
VRMS L-N
Installation
RECOMMENDED
CIRCUIT BREAKER
RATING (MAX.)
40A RMS
20A RMS
50A RMS
50A RMS
40A RMS
20A RMS
40A RMS
40A RMS
20A RMS
20A RMS
20A RMS
20A RMS
F1-F3
RECOMMENDED
FUSE
CIRCUIT BREAKER
RATING
RATING (MAX.)
40A
40A RMS
20A
40A RMS
40A
40A RMS
20A
40A RMS
20A
20A RMS
20A
20A RMS