Figure 76 Sensor Calibration / Setup Parameters - Emerson Liebert Challenger 3000 User Manual

Intelligent communications & monitoring for liebert challenger 3000, liebert challenger itr and liebert ds
Hide thumbs Also See for Liebert Challenger 3000:
Table of Contents

Advertisement

Digital Scroll 2 NTC—This parameter adjusts the digital scroll 1 NTC reading from the actual sen-
sor to compensate for any error or drift of the sensor.
Calibrated Digital Scroll 2 NTC—This parameter shows the adjusted Digital Scroll 1 NTC sensor
value. This value is the actual sensor reading (+ or -) the offset "Digital Scroll 1 NTC".
Figure 76 Sensor calibration / setup parameters - Page 2
SENSOR CALIBRATION/SETUP (page 2 of 3)
S612
S613
S614
S615
S616
S617
S618
S619
S620
S621
S622
Optional Sensor A, B & C—This parameter adjusts the reading from the actual sensor to compen-
sate for any error of the sensor or to match other sensors in the room.
Calibrated Optional Sensor A, B & C—This parameter shows the adjusted value of the sensor.
This value is the actual sensor reading (+ or -) the offset.
Optional Sensor B &C Type—This parameter currently only supports the "TH" Temperature /
Humidity sensor type.
PASSWORD (Actual Level 3)
Optional Sensor A 1
Calibrated Optional Sensor A 1
Optional Sensor A 2
Calibrated Optional Sensor A 2
Optional Sensor B Type
Optional Sensor B 1
Calibrated Optional Sensor B 1
Optional Sensor B 2
Calibrated Optional Sensor B 2
Optional Sensor C Type
for next/previous unit
then
to change parameter
UNIT 01
to select parameter
to confirm
85
Service Menu Parameters
????
+0°F
72°F
+0.0 %
49.5 %
TT
+0°F
°F
+0.0°F
°F
TT