Spare Part List
Spare Parts—The spare parts lists contains a detailed description and part number that can be used
to order parts for the unit. These part numbers are specific to each model and option installed on the
unit.
Event Log
Event Log—The event log displays all events and actions that have been generated by the unit.
When multiple units are networked you will see the event log of the whole system. Each event shows
the unit that generated the alarm, time and date stamp, a description and the event type
View Network
View Network—The view network screen provides an overview of the Liebert iCOM network and a
status of each unit. This screen will provide the unique unit name given to the unit. If no name is
given, then only the unit number will be displayed.

Figure 36 Set alarms screen

SET ALARMS (page 1 of 1)
U201
U202
U203
U204
U205
U206
U207
U208
U209
U210
U211
Return Sensor Alarms—This parameter enables or disables the return sensor alarms. When
enabled the return temperature and humidity values will be compared to a high and low setting.
High Return Temperature—This parameter is visible when the return sensor alarm is enabled.
When enabled the high temperature alarm allows a user to adjust the point at which the actual
return temperature activates a High Temperature Alarm.
Low Return Temperature—This parameter is visible when the return sensor alarm is enabled.
When enabled the low temperature alarm allows a user to adjust the point at which the actual return
temperature activates a Low Temperature Alarm.
High Return Humidity—This parameter is visible when the return sensor alarm is enabled. When
enabled the high humidity alarm allows a user to adjust the point at which the actual return humid-
ity activates a High Humidity Alarm.
Low Return Humidity—This parameter is visible when the return sensor alarm is enabled. When
enabled the low humidity alarm allows a user to adjust the point at which the actual return humidity
activates a Low Humidity Alarm.
Sensor A Alarms—This parameter enables or disables the alarms for reference sensor A. When
enabled the sensor A temperature and humidity values will be compared to a high and low setting.
High Temperature Sensor A—This parameter is visible when the sensor A alarm is enabled. When
enabled the high temperature alarm allows a user to adjust the point at which the actual sensor A
temperature activates a High Temperature Alarm.
PASSWORD (Actual Level 0)
Return Sensor Alarms
High Return Temperature
Low Return Temperature
High Return Humidity
Low Return Humidity
Sensor A Alarms
High Temperature Sensor A
Low Temperature Sensor A
High Humidity Sensor A
Low Humidity Sensor A
for next/previous unit
then
to change parameter
UNIT 01
to select parameter
to confirm
54
User Menu Parameters
????
Enable
80°F
65°F
60.0%
40.0%
Disable
°F
°F
%
%