Figure 83 Options setup parameters - Page 2
OPTIONS SETUP (page 2 of 3)
S412
S413
S414
S415
S416
S417
S418
S419
S420
S421
S422
Humidification Enabled—This parameter enables or disables humidification.
Infrared Flush Rate—This parameter shows the amount of makeup water supplied to an infrared
humidifier as a percentage of the humidifier capacity. This value can be set from 110-500% (default is
150%). Higher flush rates reduce mineral deposit buildup in the humidifier pan.
Humidifier Steam Rate—(HPM and PEX only) On units with variable capacity steam bottle
humidifiers, this parameter allows the humidifier capacity to be reduced as a percentage of nominal
humidifier capacity.
Humidifier Control—This parameter is used for HPM and PEX units only.
Humidifier Bottle Flush Time—This parameter is used for HPM and PEX units only.
Humidifier Bottle Manual Flush—This parameter is used for HPM and PEX units only.
Dehumidification Enabled—This parameters selects if the compressor and / or valve will be used
to dehumidify when the humidity is above setpoint.
Auto Restart Enabled—This parameter when set to "Yes" restarts the unit after a power cycle.
When this parameter is set to "No" then the unit will not restart (Turn On) after a power cycle.
Single Unit Auto Restart—This parameter sets a time delay for the unit to restart when the Auto
Restart Enabled is set to "Yes". The delay begins once the boot process has completed. This parameter
allows units to be staggered On to reduce the amount of simultaneous power consumption after a loss
of power.
On-Off Enabled—This parameter disables the power button on the front of the display. The default
configuration is "On".
PASSWORD (Actual Level 3)
Humidification Enabled
Infrared Flush Rate
Humidifier Steam Rate
Humidifier Control
Humidifier Bottle Flush Time
Humidifier Bottle Manual Flush
Dehumidification Enabled
Auto Restart Enabled
Single Unit Auto Restart
On-Off Enabled
for next/previous unit
then
to change parameter
UNIT 01
to select parameter
to confirm
91
Service Menu Parameters
????
Yes
150%
%
sec
No
Yes
5sec
Yes
Need help?
Do you have a question about the Liebert Challenger 3000 and is the answer not in the manual?