Figure 49 Standby Settings / Lead-Lag Parameters Screen - Emerson Liebert Challenger 3000 User Manual

Intelligent communications & monitoring for liebert challenger 3000, liebert challenger itr and liebert ds
Hide thumbs Also See for Liebert Challenger 3000:
Table of Contents

Advertisement

Figure 49 Standby settings / lead-lag parameters screen

STANDBY SETTINGS / LEAD-LAG
S501
S502
S503
S504
S505
S506
S507
S508
S509
S510
S511
Number of Standby Units—This parameter selects the number of units that will be in Standby
mode. When a unit is in standby mode the fan will be off and no cooling will be provided.
Rotation Frequency—This parameter controls when a rotation will occur between the standby
units and the operating units within a network.
Rotate at (hour)—This parameter sets the hour of the rotation
Rotate at (minute)—This parameter sets the minute of the rotation
Rotate by—This parameter determines the number of positions to rotate by. Example: If there are 6
units in a unit to unit network and units 1, 3 & 5 are in standby and this parameter is set to "1" then
at the next rotation units 2, 4,& 6 will be placed into standby and 1, 3 & 5 will become operational.
Cascade Units—This parameter when set allows units to activate from Standby mode if the room
temperature is unable to be maintained by the non-standby units. If yes is selected then the cascade
units can perform all functions when activated from standby. This parameter can also be set for Cool-
ing Only or Cool / Heat only.
Start all Standby Units by HT—This parameter activates all units to cool when a High Tempera-
ture alarm occurs.
See 3.9.1 - Calculation of Next Maintenance and Diagnostics for details on these menus.
PASSWORD (Actual Level 0)
Number of Standby Units
Rotation Frequency
Rotate at (hour)
Rotate at (minute)
Rotate by
Perform one Rotation
Cascade Units
Start all Standby Units by HT
for next/previous unit
then
to change parameter
to select parameter
to confirm
67
Service Menu Parameters
SYSTEM
????
0
No
00
00
1
No
No
No

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Liebertchallenger itrLiebert dsLiebert icom

Table of Contents