Control Types; Temperature And Humidity Control Types - Emerson Liebert Challenger 3000 User Manual

Intelligent communications & monitoring for liebert challenger 3000, liebert challenger itr and liebert ds
Hide thumbs Also See for Liebert Challenger 3000:
Table of Contents

Advertisement

Reheat During Dehumidification
Hot gas reheat or hot water reheat will start as described in 3.4 - Temperature Control—Reheat,
when the temperature decreases during the dehumidification process.
The parameter Electric Reheat Operation defines how the heaters react in case the temperature
decreases during the dehumidification process. This parameter does not impact SCR reheat opera-
tion. The Electric Reheat Operation parameter is in the Advanced menu under Factory Settings and
should not be adjusted without factory approval.
No—No electric reheat allowed during dehumidification process.
Delayed—This setting applies only to two-compressor units with BOTH compressors selected for
dehumidification. The electric reheats are prevented from turning on until Low Limit 1 is reached. At
this condition, one stage of dehumidification is disabled and the reheats are activated. At Low
Limit 2, both stages of dehumidification are disabled. When Delayed is selected on units with a single
compressor selected for dehumidification (Dehumidification With Comp Setting: 1, 2, and 1 or 2), the
reheats will operate in the same manner as they do for Staged as described below. Delayed is the
default setting for Liebert DS units.
Staged—This setting applies to one or two compressor units. Electric heaters will stage as described
in 3.4.1 - Three-Stage Electric, Hot Gas and Hot Water Reheat. Staged is the default setting for
Challenger 3000 units. On two compressor units with staged reheat selected and Dehumidification
With Comp set to BOTH, the control allows for operating two compressors and reheats simultane-
ously. It is very important that electrical service to the unit be sized and wired for this option if
selected.
WARNING
!
If the electrical service to the unit is not properly sized, it could trip the building circuit
breakers (or fuses) or, in extreme cases, damage the building wiring. This Warning applies
only when the Dehumidification With Comp is set to BOTH and the Electric Reheat
Operation is set to Staged. Consult factory before making any changes to the default settings.
3.6

Control Types

3.6.1

Temperature and Humidity Control Types

The Liebert iCOM control has three Temperature and Humidity Control Types: Proportional, PI and
Intelligent. Each control type affects the timing and intensity of the cooling/heating and humidify-
ing/dehumidifying operations. The Control Type parameter is in the Service menu under Setpoints.
Proportional—If Proportional Control is selected, the percent cooling/heating requirement is deter-
mined by the difference between the air temperature sensor reading and the temperature setpoint. As
the air temperature rises above the temperature setpoint, the percent cooling required increases pro-
portionally (from 0 to 100%) over half the programmable temperature proportional band (See 3.2.1 -
Temperature Proportional Band). The percent heating requirement (0 to -100%) is determined
the same way when the air temperature falls below the setpoint. The humidifying/dehumidifying
operations are controlled in the same manner as the cooling/heating operations; however, the humid-
ity sensors, setpoints and proportional bands are utilized. The Proportional control type is commonly
selected on compressorized units.
PI—If PI Control is selected, the percent cooling/heating requirement is calculated by adding
together two individual terms, proportional and integral. The proportional term is calculated in a
manner similar to the previously described Proportional control. The integral term (sometimes called
"reset action") is calculated by measuring how much and for how long the air temperature/humidity
has been above or below the setpoint. If the actual air temperature/humidity is above the setpoint, the
percent requirement is slowly but continuously increased until the total is sufficient to bring the
return room air back to the setpoint. This control type is commonly selected on freecooling and dual-
cool units.
Intelligent—If Intelligent Control is selected, the air temperature/humidity is controlled at or near
the setpoint. The percent temperature/humidity adjustment required is calculated based on logic that