Wall-Mount Large Display
Only large displays can be used for remotely monitoring and controlling cooling units connected on
the same network. Each wall-mount large display requires 120V input power; Liebert provides an AC
adapter wall plug. A straight-through Ethernet cable must be connected between the network switch
and the P64 port on the back of the display. This will enable control and monitoring capabilities to
any cooling unit connected to the network.
Combining Large and Small Displays on a U2U Network
Setting up a network of cooling units equipped with large and small displays requires a network
switch. The controls are to be connected to the switch as described above.

Figure 30 Wiring a small display for stand-alone operation

Small Graphics Display
On Unit Accent
Stand-Alone Unit
P66 P67
CAN CAN
P61
P18
P65
iCOM
Microprocessor and I/O Board
P54
TB1
P22
P38
P39
P53
P51
P4
P52
Unit Electronics Compartment
48
Installing a Liebert iCOM Unit-to-Unit Network
6-Wire Cable
P63
E5
P64
P66
E1
E4
E2
E3
182964